Algas-SDI Operations and Maintenance Manual – P/N – 52634 

 

4- 7 

Maintenance 

 

       

4

 

Cleaning the Filter (refer to Figure 1) 

When the unit is dirty it must be cleaned.  For proper cleaning, the stainless steel 
filter must be soaked and reverse flushed. 

RECOMMENDED PROCEDURE 

 

1.  Open the bypass valve, close the Filtaire inlet and outlet valves. 

2.  When bleeding the FILTAIRE, connect a hose or drainpipe from the drain 

valve to a safe container with a vent.  Make a good connection and bleed the 
material to the container  

CAUTION 

 

PRESSURE MUST BE ZERO FOR THE FILTAIRE TO BE REMOVED.  
CONTENTS UNDER PRESSURE ARE DANGEROUS. 

 

 

3.  Close the drain valve. 

4.  Remove Filtaire from the system and place in a cleaning area. 

5.  Cap the inlet. 

6.  Fill the unit with kerosene or a similar light solvent and allow it to soak for 24 

hours. 

7.  Reverse-flush the unit (flush from outlet flange) with kerosene until the 

Kerosene is clear and no residue is left. 

8.  After flushing, allow the kerosene or solvent to drain completely and let the 

unit dry.  Air can be pumped through the unit to dry it thoroughly.  Kerosene 
or solvent must not enter the propane system. 

9.  Remove the inlet cap. 

10.  Re-install the unit. Connect the inlet and outlet.  Close the blow-down drain. 

11.  Open the Filtaire inlet and outlet valves and close the bypass valve. 

12.  The FILTAIRE is operational. 

 

 NOTE:  Maintenance form is provided to note maintenance dates and 

operation pressures. 

 

CAUTION 

 

THE CONTENTS OF THE FILTAIRE ARE FLAMMABLE NEVER 
CLEAN THE UNIT WHEN THERE IS A SOURCE OF IGNITION IS 
PRESENT - ELECTRICAL SPARK OR FLAME. 

 

 

Summary of Contents for FILTAIRE OIL DEMISTER

Page 1: ...al Innovative liquid vaporizing and gas mixing solutions 151 South Michigan Street Seattle Washington USA 98108 Tel 206 789 5410 Fax 206 789 5414 Web www algas sdi com FILE MANUAL PN 52634 REV 01 28 1...

Page 2: ...rough the system blow down drain Residual heavy end hydrocarbons with boiling points higher than pure LPG are trapped by the filter and fall to the bottom for removal A complete FILTAIRE system consis...

Page 3: ...it downstream of the vaporizer and the first stage regulator Mount it level for the filter to work efficiently 2 Insulation may be required depending on gas pressure outside temperature and system req...

Page 4: ...Installation 2 4 Algas SDI Operations and Maintenance Manual P N 52634 Figure 3 General Equipment FILTMAN4 dwg...

Page 5: ...e system Those using the system must establish the draining schedule A general rule of thumb used to help establish the draining schedule is to measure the amount of heavy end hydrocarbons drained aft...

Page 6: ...ccumulated significant amount of residue and must be cleaned to keep on operating properly In general a FILTAIRE must be cleaned every 6 months The frequency of cleaning will greatly depend on the qua...

Page 7: ...cleaning area 5 Cap the inlet 6 Fill the unit with kerosene or a similar light solvent and allow it to soak for 24 hours 7 Reverse flush the unit flush from outlet flange with kerosene until the Kero...

Page 8: ...8 Algas SDI Operations and Maintenance Manual P N 52634 Table 2 Maintenance Form DATE DATE DRAINED AMOUNT DRAINED PRESSURE DATE CLEANED SPARE PARTS ASDI PN 30897 Float Switch ASDI PN 30641 Pressure Ga...

Page 9: ...can be used to shut down the system if liquid continues to increase in the reservoir This same system can be used to provide an additional safety that will prevent liquid propane from getting into con...

Page 10: ...Options 5 10 Algas SDI Operations and Maintenance Manual P N 52634 Figure 4 Options A FILTMAN5 dwg...

Reviews: