Installation
2-6
Algas-SDI Operation and Maintenance Manual
– P/N - 52642
Figure 3
– Installation – 40/40H, 80/40H, and 120/60H vaporizers
CAUTION
The entire installation must be leak tested prior to operating the
system.
NOTE
Do not connect this vaporizer to a storage tank that has been used
in vapor withdrawal service until the tank has been emptied and all
sediment and heavy ends have been cleaned from it.
LIQUID SUPPLY LINE
(
see Figure 3
)
The liquid supply line should be adequately sized for the service.
Table 2
– Recommended Liquid Supply Line Size (Nominal Pipe Size)
Liquid Line Length Ft. (m)
Up to 50 (15) 50-150 (15-36) 150-250 (36-76)
40/40H Vaporizers
3/4
” (DN20)
1
” (DN25)
1
” (DN25)
80/40H Vaporizers
3/4
” (DN20)
1” (DN25)
1-
1/4” (DN32)
120/60H Vaporizers
1” (DN25)
1-1/4
” (DN32)
1-
1/2” (DN40)
VAPOR DISTRIBUTION LINE
(
see Figure 3
)
The vapor distribution line should be adequately sized for the service.
Table 3
– Recommended Vapor Distribution Line Size (Nominal Pipe Size)
Gas Line Length Ft. (m)
Up to 50 (15) 50-150 (15-36) 150-250 (36-76)
40/40H Vaporizers
1” (DN25)
1-
1/2” (DN40)
2” (DN50)
80/40H Vaporizers
1-
1/4” (DN32) 1-1/2” (DN40)
2” (DN50)
120/60H Vaporizers
1-
1/2” (DN40)
2” (DN50)
2-
1/2” (DN80)
Summary of Contents for Direct Fired 120/60H
Page 4: ...This page left intentionally blank...
Page 6: ...This page left intentionally blank...
Page 9: ...This page left intentionally blank...
Page 42: ...APPENDIX A TECHNICAL INFORMATION...
Page 43: ...Figure 13 40 40H Vaporizer Replacement Parts 1 2 3 4 5 6 10 8 9 11 12 13 14 15 16 24...
Page 55: ......