Setting Up Power over Ethernet Hardware
Installing and Managing Power over Ethernet (PoE)
page 3-12
OmniSwitch 7700/7800 Hardware Users Guide
April 2005
2
Attach the flanges to the power shelf using the Phillips-head screws provided. Be sure to tighten each
of the screws firmly using a Phillips screwdriver.
3
After both rack-mount flanges are secured to the unit, mark the holes on the rack where the power shelf
is to be installed.
4
Lift and position the power shelf until the rack-mount flanges are flush with the rack post.
5
Align the holes in the flanges with the rack holes that were marked in step 3.
6
Once the holes are aligned, insert a rack mount screw (not provided) through the
bottom hole of each
flange
. Tighten both screws until they are secure.
Note.
Be sure to install the screws in the
bottom hole
of each flange, as shown, before proceeding.
7
Once the screws at the bottom of each flange are secure, install the remaining two rack mount screws.
Be sure that all screws are securely tightened.