![Alcad AT30 SERIES Operating And Service Instructions Download Page 94](http://html1.mh-extra.com/html/alcad/at30-series/at30-series_operating-and-service-instructions_2890044094.webp)
APPENDIX D
90
RECOMMENDED FLOAT AND EQUALIZE VOLTAGES
This table contains suggested values for commonly used batteries. Consult your battery
manufacturer's documentation for specific values and settings for your battery type.
Battery Cell Type
Recommended
Float Voltage/cell
Recommended
Equalize Voltage/cell
Antimony (1.215 Sp. Gr.)
2.17
2.33
Antimony (1.250 Sp. Gr.)
2.20
2.33
Selenium (1.240 Sp. Gr.)
2.23
2.33 - 2.40
Calcium (1.215 Sp. Gr.)
2.25
2.33
Calcium (1.250 Sp. Gr.)
2.29
2.33
Lead
-Acid Types
Absorbed / Gelled Electrolyte *
(sealed lead acid type)
2.25
*
Nickel Cadmium
1.42
1.47
* Sealed lead-acid battery types should not be used in ambient temperatures above 95
°
F / 35
°
C, and should not normally be equalized. Consult your battery manufacturer's
documentation for specific equalizing recommendations.
TEMPERATURE COMPENSATION
If batteries are to see temperature variations during charging, a temperature
compensation option (A10) is recommended. If this option is not part of your charger,
manual adjustments should be made. Please refer to the equation and table below for
temperature-adjusted voltages.
temperature-adjusted voltage = charge voltage x K
Temperature
(°F)
Temperature
(°C)
K
(Lead Acid)
K
(Nickel Cadmium)
35
1.7
1.058
1.044
45
7.2
1.044
1.034
55
12.8
1.031
1.023
65
18.3
1.017
1.013
75
23.9
1.003
1.002
77
25.0
1.000
1.000
85
29.4
0.989
0.992
95
35.0
0.975
0.981
105
40.6
0.961
0.970