![Alcad AT30 SERIES Operating And Service Instructions Download Page 14](http://html1.mh-extra.com/html/alcad/at30-series/at30-series_operating-and-service-instructions_2890044014.webp)
INSTALLING THE AT30
10
1.6. CHANGING THE TRANSFORMER TAPS
IMPORTANT: The AT30 Battery Charger is designed for a single ac
supply voltage. Note the ac voltage listing on the data nameplate
and the tag attached to the front panel. If your particular ac supply
voltage does not match your AT30 ac input requirements, you
MUST change the ac input circuit breaker (and/or fuses) and the
input surge suppressors. In addition, you must replace or rewire the
transformer as described below. Failure to use the properly rated
components may damage the charger.
NOTE
: If your AT30 Battery Charger was ordered with 480 Vac -
60Hz input or 220 Vac - 50/60 Hz input the transformer accepts
only the listed voltage.
Do not attempt to rewire these
transformers.
If a different ac input voltage is desired for the
AT30, please contact your sales representative for ordering
replacement parts.
Before you connect ac power to the AT30, check the wiring of the main
transformer (T1) to be sure it is connected for the desired ac input voltage.
The main transformer was wired at the factory for the input voltage
specified and listed on the data nameplate.
If your AT30 was ordered with 208/240 Vac - 60Hz input and you need to
change the factory-wired input voltage, do so by changing the jumpers on
the main transformer (T1). If your AT30 was ordered with 380/416 Vac -
50/60 Hz and you need to change the factory-wired input voltage, please
consult the factory for special instructions.
NOTE
: Before starting work, disconnect and lock out all external
ac and dc power sources to the AT30. Note that just turning off
the front panel ac and dc circuit breakers is not sufficient to
eliminate live voltages inside the enclosure. Use a voltmeter at
the ac terminals TB1-L1, TB1-L2 & TB1-L3 (ac), and the dc
terminals TB1(+), TB1(-), the remote sense terminals (+/-), and
any external wiring, to alarm relay contacts to verify that no
voltage is present inside the enclosure.