INSTALLING THE AT30
8
1.5.3. Rack-Mounting the AT30
(Style-5018 enclosure only)
AT30 battery chargers housed in the floor-mounted Style-5018 enclosure
can be installed in most relay racks with standard EIA hole spacing. You
do not need to modify the standard Style-5018 enclosure for rack
mounting, but a special rack-mounting kit (
EI0193-03
) is required. For
kit availability see ordering information in Appendix B on page 65. Each
kit includes two (2) mounting brackets, hardware and special instructions
with for the rack mounting procedure. In planning for rack mounting of
the AT30, you should consider the following:
1. The rack must be strong enough to properly support the weight of the AT30.
The weight of your AT30 may be different from the table value, depending
on options or accessories you ordered. See the Weight Table located in
Section 1.4 on page 3.
2. Placement of conduit entrances. Note the standard pre-fab conduit knockouts
located on the sides of the charger. See the outline drawing (
JE5085-00
) in
Appendix C, on Page 66. Be sure the knockouts on the sides or bottom of the
charger are accessible after the charger is rack mounted.
3. The location:
•
Should be free of drips and splatter. If dripping liquids are a problem,
install a drip shield kit. For kit availability see ordering information in
Appendix B on page 65.
•
Should be between 32 and 122 °F / 0 and 50 °C, with relative humidity
between 5 and 95% non-condensing.
•
Must be free of flammable or explosive materials.
4. Maintain at least 6in / 152mm of free air on top, bottom and both sides of the
enclosure for air cooling.
5. Allow 36in / 914mm front clearance for access to the charger for operation
and maintenance.
PROCEDURE
1. Mount the two (2) relay rack-mounting brackets to
the sides of the Style-5018 enclosure, using the four
(4) pre-fab knockouts on each side as guides.
2. Mount the brackets to the AT30, using the supplied
0.25in / 6.4mm hardware and tighten securely.
3. Locate the charger/bracket assembly onto the front
face of the 23in / 584mm EIA relay rack, and
mount using appropiate hardware (not supplied).
4. See the diagram on the opposite page for the rack-
mounted Style-5018 enclosure footprint and
mounting pattern.