INSTALLING THE AT30
18
1.10. WIRING TO THE REMOTE ALARM CONTACTS
Built-in Summary (Common) Alarm Relay
(standard)
The Main Control PC
Board (A1), mounted on
the back of the front door,
is equipped with one form
C Summary Alarm contact
(TB3) that transfers for
any alarm.
Follow the procedure
below to wire an
annunciator to this
contact. See Section 2.2.7
for a description of the
alarm functions.
PROCEDURE
1. Allow 30in / 762mm of wire inside the enclosure (excess will be trimmed).
2. Route wires to front door by following the existing harness through the door
hinge as shown. Use (2) wire ties and allow a 4-6in / 102-153mm loop for
the hinge.
3. Trim wires to the proper length for connecting to TB3. Strip 0.25in / 6.4mm
of insulation from the wires. Make the connections at TB3, and securely
tighten the screws.
NOTES:
1. Alarm contacts are rated at 0.5A / 125 Vac or Vdc.
2. Terminal block is a compression type, accepting wire sizes #22-14 AWG.
3. Terminals are labeled in non-alarm condition.