Section 6
Specifications

6.1 Electrical Specifications

6.1.1 Input Voltage (B1 and B2)

12-24VDC Nominal

Note:  B1 MUST be 12V or 

higher.

6.1.2 Input Current (B1 and B2)

14A maximum per buss

6.2 Temperature Specifications

6.2.1 Ambient Temperature Range

0

º

C to 49

º

C (32

º

F to 120

º

F)

6.2.2 Ambient Humidity

93% at 32

º

C (90

º

F) Maximum

6.3 Mechanical Specifications

6.3.1 Weight

0.10 LBS (Not including
hardware or cables)

6.3.2 Size

4.83”L x 2.10”W x 0.75”H

Note:  Width includes terminal 
block overhang of 0.1”

6.3.3 CAD Drawing

Figure 6.3.1

4.825"

4.50"

1

.5

0

"

2

.0

0

"

FAIM Installation Instructions
2009/10/30 16:12:34

52-382 Rev A.01

Page 15 of 15

AlarmSaf

 65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com

Summary of Contents for PS5-M

Page 1: ...M Power Supply Battery Charger with Fire Alarm Input Module Installation Manual This Installation manual is made up of the following separate Installation Instructions for the Power Supply and Fire Al...

Page 2: ...USS 1 J4 ABC COM FLT AC FLT COM FLT GND FLT AC FLT VOLTAGE SELECT 24V 12V BAT DETECT EARTH GND DETECT AC ON EARTH HOT NEUTRAL J1 BATTERY FUSE Model PS5 M Power Supply Battery Charger Operating and Ins...

Page 3: ...n a manner which prevents unintentional operation from employees or other personnel working about the premises by falling objects by building vibration and by similar causes NOTICE This equipment is n...

Page 4: ...3 8 Fusing 11 3 7 Fault Reporting Terminals 10 3 6 Battery Terminals 10 3 5 Output Terminals 9 3 4 ABC Connectors and Harnesses 8 3 3 AC Input Connection 7 3 2 Connector Descriptions and Electrical R...

Page 5: ...her of two available power busses Buss 1 or Buss 2 All units can charge up to 80 AH of battery within 48 hours 40 AH in 24 hours while supplying full rated load Full fault detection including battery...

Page 6: ...ts of the Local Authority Having Jurisdiction LAHJ FCC Compliance This equipment has been tested and found to comply with the limits for Class A digital device pursuant to Part 15 of FCC rules These l...

Page 7: ...ax Output 80 mA Maximum Plus total output load including accessory boards Standby Load While on Battery 170W max Input Power All Models 120 VAC or 230 VAC nominal 50 60 Hz Input Voltage Product Use Wh...

Page 8: ...Hz Must be configured for 230 VAC prior to use See Fig 3 3 1 5 Pin AC Line connector J1 Rating Description Terminal Connector Figure 3 2 1 JP3 DC DC BAT BAT JP5 JP6 JP7 BUSS 2 BUSS 1 J4 ABC COM FLT AC...

Page 9: ...put or damage to the supply will occur See Figure 3 3 1 Note The AC input connector is a convenient means for AC disconnect since the connector is fully shrouded when disconnected Note The Green or Gr...

Page 10: ...or Buss 2 3 4 2 Cable Types ABC 04 18 inches Brown 00522 8 8 ABC 03 8 inches Brown 00521 8 8 Description Length Color AS PN Cable Type ABC 03 Used to connect the PS5 M to an accessory board or to conn...

Page 11: ...here are no batteries on the PS5 M it is normal for there to be no voltage on the battery terminals The charger does not enable until it senses a battery on the terminals Note Connecting batteries in...

Page 12: ...FLT GND FLT AC FLT COMMON FAULT FIELD WIRING TERMINALS AC FAULT FIELD WIRING TERMINALS C NC NO C NC NO No Fault Fault Fault Internal Fault No Fault Fault Reversed Battery Connection No Fault Fault Bl...

Page 13: ...available Automotive Miniature fuses Type ATM Both fuses are rated at 15A ATM 15 The AC Input fuse is a soldered in non replaceable fuse If it is determined that this fuse has opened the PS5 M board...

Page 14: ...mately inch 3 Using the two upper keyholes mount the cabinet over the two screws 4 Mark the two lower holes remove the cabinet and drill the lower mounting holes 5 Mount the cabinet install the remain...

Page 15: ...ing Locate the battery terminals These terminals are non removable and accept wire sizes between 12 and 22 AWG Polarity is notated on the PCB If the PS5 M is set for 12 VDC connect a single 12V batter...

Page 16: ...NABLE AC PRESENCE VISUAL INDICATOR 12V 24V Figure 5 1 1 5 2 Jumper Settings For proper operation the jumpers on the PS5 M should be set appropriately These jumpers may be set with the unit powered or...

Page 17: ...utput Green DC Output DC OK D15 Lights when AC voltage is present on the input Green AC Power AC ON D19 Conditions Color Description LED 5 3 1 AC ON D19 For safety reasons this LED illuminates any tim...

Page 18: ...ble s Improper ABC cable connection Verify that output current is less than the rated current Excessive loading on output Verify fuse is intact Check wiring integrity before replacing fuse Blown batte...

Page 19: ...harge 6 1 6 Maximum Battery Charger Capacity 80 Amphours 48 hour charge 6 1 7 Maximum Battery Charge Current 2A max at 12 or 24 VDC nominal 6 2 Temperature Specifications 6 2 1 Ambient Temperature Ran...

Page 20: ...NPUT V V AlarmSaf c 2006 SAME TYPE AND RATING REPLACE FUSES ONLY WITH UTILISER UN FUSIBLE DE RECHANGE DE MEME FLT FAI B1 B1 B2 B2 RET PWR LTD DC1 DC2 DC1 DC2 DC1 DC2 B1 B2 FAI ATM 15 L BUSS 2 CONNECT...

Page 21: ...or other personnel working about the premises by falling objects by building vibration and by similar causes NOTICE This equipment is not intended for use within the patient care areas of a Health Ca...

Page 22: ...put Terminals 9 3 5 Input Terminals 9 4 Installation 10 11 4 1 Mounting 10 4 2 Wiring 11 4 3 Labeling 11 5 Operating the FAIM 12 14 5 1 Jumper Configuration 12 5 2 Visual Indicators 13 5 3 Troubleshoo...

Page 23: ...on power limited output and one 1 6A PTC protected power limited output These outputs drop power upon the FAIM receiving a valid input signal Two methods of connection of the output to the ABC buss ar...

Page 24: ...osed Circuit Television Equipment Canadian Standards ULC S527 Standard for Control Units for Fire Alarm Systems ULC S318 Standard for Power Supplies for Burglar Alarm Systems CAN CSA C22 2 No 107 1 01...

Page 25: ...er supplies and jumper selections Outputs Power Input 12 24VDC Nominal 14 Amps maximum Control Input 9 33VDC 3 3mA Maximum Inputs Product Use When installed in accordance with all standards listed in...

Page 26: ...ABC Input or Output P2 12 24V Nominal at 14A per Buss controlled by base supply s ABC Input or Output P1 Rating Description Terminal Connector Fig 3 2 1 TB2 P1 P2 D1 F1 D2 J1 J2 D12 D13 J3 D10 TB1 MOD...

Page 27: ...ipment 3 3 4 Cable Types ABC 06 18 inches Red A099071 6 8 ABC 05 8 inches Red A099070 6 8 ABC 04 18 inches Brown A099069 8 8 ABC 03 8 inches Brown A099068 8 8 ABC 02 18 inches White A099063 6 6 ABC 01...

Page 28: ...e FAIM s input terminals TB1 provide the control for the DC1 and DC2 outputs The input can be selected for fail safe or fail secure as well as for voltage input dry contact or open collector activatio...

Page 29: ...doffs and secure using the included 6 32 x 3 8 screws 3 Connect ABC cable s appropriately See section 3 3 4 1 1 Mounting to an approved power supply 1 If not already present install the four 6 32 x 3...

Page 30: ...he header Connect the wiring for the equipment to be powered to the terminal block The PC board is labeled with the output numbers and polarity See also Sections 3 2 and 3 4 Replace the terminal block...

Page 31: ...required to reset the FAIM In addition to this jumper setting a specific wiring method is required to use the latching feature See Appendix A for details on wiring the FAIM s input terminals in the la...

Page 32: ...available when lit DC2 D12 Indicates that the DC2 output has power available when lit TB2 P1 P2 D1 F1 D2 J1 J2 D12 D13 J3 D10 TB1 MODE FAI BUSS FAI FAIM 38 137 Rev B01 B A FAI INPUT V V AlarmSaf c 20...

Page 33: ...put is activating properly Input not being activated Verify proper input and output jumper settings Improper Jumper Settings Input not operating as expected Verify correct state of input and input wir...

Page 34: ...o 49 C 32 F to 120 F 6 2 2 Ambient Humidity 93 at 32 C 90 F Maximum 6 3 Mechanical Specifications 6 3 1 Weight 0 10 LBS Not including hardware or cables 6 3 2 Size 4 83 L x 2 10 W x 0 75 H Note Width...

Page 35: ...arious wiring methods Verify all jumpers are set properly Remote normally open dry contact trip using the internal voltage source of the FAIM Internal FAI Mode jumper J1 must be set to the right Remot...

Page 36: ...mper J1 must be set to the right Remote normally closed dry contact trip using the internal voltage source of the FAIM Internal FAI Mode jumper J1 must be set to the right Remote normally open dry con...

Reviews: