PDFT Fire Transfer Relay with EOL Trigger 

 

 
 

 
 
Alarm Controls Corporation 
19 Brandywine Drive 
Deer Park, NY 11729

 

500-33320_A   Installation specifications subject to change without notice

Phone: (800) 645-5538

[email protected]

www.alarmcontrols.com

Page 1 

 

 

 

 

 

Features: 

 

Non Latching or Latching mode 

 

12 or 24VDC Operation 

 

Reverse polarity protected 

 

Normally ON & Normally OFF Output  

 

Output LED’s indicate condition 

 

Outputs can be Triggered with: 

  1.  N/O or N/C Switch with Supervised (EOL) 
  2.  N/C Switch with (OVR) over ride 
  3.  N/C Switch with AUX-IN auxiliary 
  4.  Ground on any trigger input when (GRN) 
  Jumper is enabled 

 

Form C Contacts Indicates Trigger Status 

 

12 Amp Transfer Relay Contacts 

 

Lifetime Warranty  -  Made in the USA  

 

UL Listed Sub Assembly for Access Control and Burglar Alarm Systems 

 

Description 

The PDFT transfers the input power from the normally ON 
output pair “-N/ON+” too the normally OFF output pair “-
N/OFF+” when triggered.  The unit is triggered when the 
supervised (EOL), end of line resistor is opened or shorted.  
The triggered form C user contacts indicate the state of the 
trigger.  A typical application of the PDFT is to place a 
distribution board on one or both of the outputs, one of our 
power supplies on the Input, then connecting the EOL at a 
fire alarm panel to transfer the power from one distribution 
board to another when the Fire alarm panel is in the alarm 
condition.  The transferred power would be used to unlock 
doors, shut down air systems, or return elevators to an exit 
floor.  

Specifications / Instructions 
Input Power “-INPUT+”: 2 Pos. Terminal block 

with self 

clamping screws will accept multiple 12awg wires

 

– Operates 

with 12 or 24vdc input.  The input current is 70ma to control 
relays plus whatever output load is.  The positive side of the 
power is connected to the swing arm of the transfer relay 
which directs the power to the proper output. 

Output Power: 4 Pos. Terminal block 

Self clamping screws 

will accept multiple 12awg wires. “-N/ON+” are normally ON 
output power.  This output is ON when the PDFT is not 
triggered.  “-N/OFF+” is normally OFF.  This output is ON 
when this unit is triggered.  The transfer relay is rated at 
15A@12v and 12A@24vdc. 

Power LED’s:

  A red LED above each output indicates which 

output is ON. 

Input Trigger EOL: 2 Pos. Terminal block 

– Will accept 14-

28awg wire.  This input must see the 2.2K ohm end of line 
resistor to be in the normal set condition.  A change in 
resistance of + or – 60% will cause the trigger relays to drop 
out in the Triggered mode.  This change in resistance is 
caused by the supervised wire between the EOL at the Fire 
panel and the PDFT being shorted or opened.  The EOL 
supervises the pair of wires. 

Input Trigger OVR: 2 Pos. Terminal block

 - Will accept 14-

28awg wire.  This pair is normally closed, can be connected 
to an override switch.  When OVR is open, unit will trigger. 

Input Trigger AUX-IN: 2 Pos. Terminal block

 - Will accept 

14-28awg wire.  This pair is normally closed and can be 
connected to an auxiliary device.  When AUX-IN is open, unit 
will trigger. 

RESET 2 Pos. Terminal block

 – Will accept 14-28awg wire.  

When this pair is shorted, input triggers do not latch.  If pair is 
open, the input triggers will latch until alarm is corrected and 
RESET is momentary closed to reset trigger. 

Jumpers RST – OVR – AUX

 are jumpers with handles to 

short adjacent terminal blocks that are not used.  You may 
move the jumper to one header to open short to enable 
adjacent terminals.  

Jumper GRN

 – This jumper is used to enable ground 

supervision in the inputs.  If the jumper is connected to both 
headers, and the mounting hole adjacent to jumper is 
connected to ground with a star washer, a ground on any of 
the input triggers will cause a trigger. 

Trigger Status Terminal block

 - Will accept 14-28awg wire.  

Form C Contact with a 3 Amp rating will indicate the 
condition of trigger.  C and NO are normally open in the 
normal energize not triggered state.  C and NC are normally 
closed in the normal energized not triggered state.  These 
contacts may be used to provide feedback to the FACP or 
other annunciating devices. 

Module dimensions

   .......................   2.23”W x 3.75”L x .8”H 

Mounting holes dimensions

   ........................   1.89” x 3.41” 

Weight

:  .......................................................................   2.2oz 

UL Approvals for PDFT 

UL 294 – Access Control System Unit 
UL 603 – Power supplies for Use with Burglar-Alarm 
Systems ULC S318-96 – Power supplies for Burglar Alarm 
Systems ULC S533-02 – Standard for Egress Door Securing 
and Releasing Devices. 

Summary of Contents for APS-300 Series

Page 1: ...LED s Quality Manufactured in the USA with a lifetime Warranty Outputs are Power Limited Provided in Standard Enclosure 14 x 8 5 x 3 5 Precise Battery Regulation for all sealed Lead Acid Battery s Bat...

Page 2: ...ndicator is a green LED which is illuminated when AC is present AC Line Primary Fuse Fuse GMA 2 5mm x 20mm 2A 250VAC Replace this fuse only while the equipment is electrically disconnected from the br...

Page 3: ...ropriate input of a UL Listed Burglar Alarm or Access control panel When DC Power is normal the negative output is an open circuit with the LED OFF When the DC output voltage drops to a point where th...

Page 4: ...f 25 from Non power Limited circuits 4 Connect DC devices to the Output Terminals Observe polarity On the distribution boards Negative is identified with a or COM The Positive is identified with or HO...

Page 5: ...battery capacity with either 12V or 24V batteries The minimum battery capacity is 4Ah and the practical limit is 24Ah UL evaluated with an 18Ah battery on the 12V configuration and 2 9Ah batteries on...

Page 6: ...APS 300 Instructions Page 6 500 33315_A...

Page 7: ...unit is triggered The transfer relay is rated at 15A 12v and 12A 24vdc Power LED s A red LED above each output indicates which output is ON Input Trigger EOL 2 Pos Terminal block Will accept 14 28awg...

Page 8: ...Red LED Indicates AC DC or Reversed DC Input on PD4C Each output has a green status LED indictor Current Draw is 6ma max per LED Circuit Breaker Models with Rated Output 1 42 Amps or below are Power L...