background image

 

APS-300 Instructions 

Page 4

 

500-33315_A 

APS-300 Series Power Supply/Charger Installation Guide 

The APS-300 with standby battery(s) provides an uninterruptible 9.8VDC-13.7VDC or 20.0VDC-27.5VDC power source.  When 
use with optional Power Distribution modules PD4C or PDFT, it can provide multiple fused outputs or Fire Interface. The DC 
output on the APS-300 power supply is Power Limited.  This makes all subsequent outputs power limited.  
 
1.  The installation of this power supply shall comply with the National Electrical Code (ANSI/NPFA 70), the Canadian Electrical 

Code, Part 1, and be in accordance with any additional requirements imposed by the local authority having jurisdiction. 

2.  For use in Indoor Location Only, Mount the Power Supply in desired location.  Using the two keyholes on the upper end and 

the two or three holes along the bottom, mount the enclosure to the wall with appropriate fasteners. 

3.  Select output voltage by shifting the jumper J1 for 12VDC or 24VDC.  

Only change output voltage when AC is OFF and 

Batteries are not connected

.  The APS-300 Series has a continuous output rating of 9.8VDC-13.7VDC at 2.8 Amps or 

20.0VDC-27.5VDC at 1.4 Amps.  If a power distribution product is used, the total current draw of these devices must be 
subtracted from the available current rating. See selection table below or individual data sheets.  Connect AC Line voltage, 
110-240VAC with Earth Ground to the Orange AC input Terminal block.  This wiring must be run in separate metal enclosed 
wiring system only.  Note, Ensure all wiring is of appropriate gauge for device being powered.  

All Power Limited circuits 

must be separated by a minimum of .25” from Non-power Limited circuits.

 

4.  Connect DC devices to the Output Terminals.  Observe polarity.  On the distribution boards Negative is identified with a (-) or 

(COM).  The Positive is identified with (+) or (HOT).  Exit the DC wiring out any of the other available knock outs keeping all 
the low voltage wiring away from the high voltage wiring and battery leads. 

5.  If supervision is desired, connect N/C Tamper switch and AC fail form “C” contacts to Security system for annunciation.  

6.  Add the current draw of the distribution boards to your load calculation to ensure your power requirements are within the 

unit’s continuous power rating.  Always check the spec sheet; but as a rule, each LED draws 6mA and each relay draws 
20mA. 

7.  Confirm with Amp meter that your total continuous current conforms to the output current rating and that each output rating is 

proper for the powered device(s).  

8.  Connect AC fail contacts to annunciate AC Status condition. 

9.  Connect appropriate standby battery(s).  Remove AC and confirm battery output to test standby battery(s). Mark installation 

date on Battery with permanent marker. 

10.  Each protected output on the optional power distribution board PD4C has a Green Status LED.  Green ON indicates ready. 

11.  To reset a tripped PTC Circuit Breaker, you may have to turn power off on outputs, or remove faulted circuit output for up to 2 

minutes.  This allows the PTC re-settable circuit breaker to cool and reset to its normal “ON” condition. 

12.  For installation and use of optional PD4C and PDFT, see separate enclosed instructions. 

CAUTION: Replace fuses as marked  
 
When calculated your total DC current be sure to add the current of any distributions options you are using.  Be sure 
your normal continuous DC current draw does not exceed the marked rating of the supply. 
Select 12/24 J1 only with AC off and Batteries disconnected. 

 

Summary of Contents for APS-300 Series

Page 1: ...LED s Quality Manufactured in the USA with a lifetime Warranty Outputs are Power Limited Provided in Standard Enclosure 14 x 8 5 x 3 5 Precise Battery Regulation for all sealed Lead Acid Battery s Bat...

Page 2: ...ndicator is a green LED which is illuminated when AC is present AC Line Primary Fuse Fuse GMA 2 5mm x 20mm 2A 250VAC Replace this fuse only while the equipment is electrically disconnected from the br...

Page 3: ...ropriate input of a UL Listed Burglar Alarm or Access control panel When DC Power is normal the negative output is an open circuit with the LED OFF When the DC output voltage drops to a point where th...

Page 4: ...f 25 from Non power Limited circuits 4 Connect DC devices to the Output Terminals Observe polarity On the distribution boards Negative is identified with a or COM The Positive is identified with or HO...

Page 5: ...battery capacity with either 12V or 24V batteries The minimum battery capacity is 4Ah and the practical limit is 24Ah UL evaluated with an 18Ah battery on the 12V configuration and 2 9Ah batteries on...

Page 6: ...APS 300 Instructions Page 6 500 33315_A...

Page 7: ...unit is triggered The transfer relay is rated at 15A 12v and 12A 24vdc Power LED s A red LED above each output indicates which output is ON Input Trigger EOL 2 Pos Terminal block Will accept 14 28awg...

Page 8: ...Red LED Indicates AC DC or Reversed DC Input on PD4C Each output has a green status LED indictor Current Draw is 6ma max per LED Circuit Breaker Models with Rated Output 1 42 Amps or below are Power L...

Reviews: