![Akytec MV210-101 User Manual Download Page 34](http://html1.mh-extra.com/html/akytec/mv210-101/mv210-101_user-manual_2887631034.webp)
Appendix D. Modbus application
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
33
Appendix D. Modbus application
Table D.1 – device parameters with register addresses
Table D.2 – used data types
Table D.3 – used Modbus functions
Table D.4 – possible data exchange errors
Table D.5 – function-specific errors
If an error occurs when receiving a request, the module sends a response to the Master with an error
code.
If the request does not comply with the Modbus specification, it will be ignored.
Table D.1. Modbus registers
Parameter
Value
Unit
Ac-
cess
Address
Data type
hex
dec
Device information
Device name (dev)
-
-
R
0xF000
61440
String32
Firmware version (ver)
-
-
R
0xF010
61456
String32
Platform name
-
-
R
0xF020
61472
String32
Platform version
-
-
R
0xF030
61488
String32
Hardware version
-
-
R
0xF040
61504
String16
Additional text information
-
-
R
0xF048
61512
String16
S/N
-
-
R
0xF084
61572
String32
MAC address
-
-
R
0xF100
61696
UINT48
Real-time clock
Time
-
s
R
0xF080
61568
DATETIME
Time zone
-
min
RW
0xF082
61570
TIMEZONE
Time (ms)
0…4294967295
ms
R
0xF07B
61563
UINT32
New time
-
s
RW
0xF07D
61565
DATETIME
Apply new time
0 - off / 1 - on
-
RW
0xF07F
61567
UINT16
Network / Ethernet
IP address
-
-
R
0x001A
26
UINT32
Subnet mask
-
-
R
0x001C
28
UINT32
Gateway
-
-
R
0x001E
30
UINT32
DNS server 1
-
-
RW
0x000C
12
UINT32
DNS server 2
-
-
RW
0x000E
14
UINT32
New IP address
-
-
RW
0x0014
20
UINT32
New subnet mask
-
-
RW
0x0016
22
UINT32
New gateway
-
-
RW
0x0018
24
UINT32
DHCP
0 - off
1 - on
2 - service button
-
RW
0x0020
32
UINT16
Battery
Voltage
0…3300
mV
R
0x0321
801
UINT16
Modbus Slave
Safe state timeout
0…60
s
RW
0x2BC
700
UINT8
Device status
Status
-
R
0xF0B4
61620
UINT32