![Akytec MV210-101 User Manual Download Page 15](http://html1.mh-extra.com/html/akytec/mv210-101/mv210-101_user-manual_2887631015.webp)
Configuration and operation
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
14
4.7 Data logging
An archive is saved as a set of encrypted log files. A log file consists of a set of records separated by line
break characters (0x0A0D). Each record corresponds to one parameter and consists of fields separated by
semicolon. The format of the record is described in Tab. 4.4.
Table 4.4. Record format
Field
Type
Size
Comment
Time
binary
4 Byte
In seconds, beginning from 01/01/2000, 00:00 (UTC+0)
Separator
string
1 Byte
Semicolon (;)
UID (parameter ID)
string
8 Byte
String of HEX characters with leading zeros
Separator
string
1 Byte
Semicolon (;)
Parameter value
string
parameter
depending
String of HEX characters with leading zeros
Separator
string
1 Byte
Semicolon (;)
Parameter status
binary
1 Byte
1 – value correct
0 – value incorrect, further processing not recommended
New line
binary
2 Byte
0x0A0D
Log files are stored in a built-in flash memory, formatted as a file system with encryption. For flash memory
specifications see section “Flash memory” in Table 3.1.
If an archive overflows, the new entry will overwrite the oldest one in the archive.
The archiving parameters are described in Tab. 4.5.
To view all logged parameters, use the toolbar item
Device information
in akYtecToolPro.
The archive can be read with via Modbus TCP using function 20 (Tab. D.3). This function allows reading one
or several records from one or several files in one request. For details on function usage see
The file number in the Modbus request should be calculated as file ID + 4096. File indexing starts with zero.
The parameter
Last log file ID
contains the ID of the archive file to which the data was last written.
The time zone is not contained in the file but can be read from the parameter
Time zone
(Tab. D.1).
Table 4.5. Archiving parameters
Parameter
Description
Range
Default value Access
Logging interval
Time interval with which the values of the
selected parameters will be recorded
10…3600 s
30
RW
Number of files
Maximum number of archive files
10…300
100
RW
File size
Log file size in Bytes
200…2048
2048
RW
Last log file ID
ID of the last written file
0…65535
−
R
4.8 Analog inputs
To configure the analog inputs, open the
Analog inputs
group in the parameter tree.
Table 4.6. AI parameters
Parameter
Description
Range
Default
value Access
Group
CJC
Reference junction compensation option
for thermocouples (Sect. 4.8.7)
On
/
Off
On
RW
Maximum sampling rate
On
– Sampling time is automatically
adjusted to the minimum possible for the
selected input signal (Sect. 4.8.1)
On
/
Off
On
RW