Akytec MV210-101 User Manual Download Page 18

 

Configuration and operation 

 

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de  

17

 

AIn INT 

AIn REAL 

* 10 

DP

 

DP – 

Decimal point offset

 specified in the range 0…7. 

 

NOTE

 

Setting the “Decimal point offset” to 6 or 7 can cause that the “AIn INT” value goes be-

yond the range -32768…32767 (or 0…65535 for unsigned presentation) and cannot be 

saved in INT16 format. This should be taken into account when setting the “Decimal point 

offset” value. 

AIn timestamp 

is a cyclic time with the 0.01 second step, stored in two bytes. The time counting starts with 

the first measuring and is reset to zero every 65536 steps, i.e. 655.36 seconds. It marks the time of the 

measurement in the channel. Using the timestamp, you do not have to take the Ethernet transmission delay 

into account (e.g. when calculating the derivation time in the PID control).  
The measured values are stored in their respective memory registers (Tab. D.1) and can be read with Mod-

bus functions 3 (0x03) or 4 (0x04). 

4.8.6  Sensor diagnostic 

The module monitors the operation of the transmitters connected to its inputs. If a malfunction is detected, 

the module transmits an error message over Ethernet. Common error cases: 

  All transmitter types – the measured values are beyond the permissible range 

  RTD or TC sensor break 

  RTD short circuit 

  Cold junction temperature is beyond the range -

40...+90 °С

 

Some transmitter errors cannot be detected: 

  Current and voltage sensor breaks. The measuring channel shows a zero value or the error "Meas-

ured value too low". 

  Due to the implemented diagnostic of a thermocouple short circuit, resistance signals below 25 

Ω

 

are considered invalid. Therefore, the resistance sensor 0...2 k

Ω

 cannot measure signals in the 

range 0…25 

Ω

 (0…1.26% of the measuring range). 

In case of an input error, the error code is written to the most significant byte of the corresponding 

AIn REAL

 

register instead of the measured value and to the 

AIn status

 register. 

Table 4.7.   Input diagnostic errors 

Error 

code 

Description 

Input 

indicator 

0xF0 

Incorrect value 

orange 

0xF6 

Data not ready. Wait for the results of the first measurement after powering on. 

orange 

0xF7 

Input disabled (Off) 

off 

0xF8 

Cold junction temperature too high 

orange 

0xF9 

Cold junction temperature too low 

orange 

0xFA 

Measured value too high 

orange 

0xFB 

Measured value too low 

orange 

0xFC 

Sensor short circuit 

red 

0xFD 

Sensor break 

red 

0xFE 

No connection with ADC 

red 

0xFF 

Incorrect calibration coefficient 

orange 

4.8.7  Reference junction compensation 

The input circuit provides an optional correction of the measured values for thermocouples using the refer-

ence (cold) junction temperature compensation (CJC). The cold junction temperature is measured by three 

Summary of Contents for MV210-101

Page 1: ...alder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de MV210 101 Analog Input Module 8 AI User guide MV210 101_2022_05_34798 1 15_EN All rights reserved Subject to technical cha...

Page 2: ...Connection with akYtecToolPro 10 4 1 1 Connection over USB 10 4 1 2 Connection over Ethernet 10 4 2 Real time clock 11 4 3 Battery 12 4 4 Ethernet 12 4 4 1 Network parameters setting using service but...

Page 3: ...stallation 21 5 1 Mounting 21 5 2 Wiring 21 5 2 1 General information 22 5 2 2 Analog inputs 22 5 2 3 Ethernet 25 6 Factory settings restoration 26 7 Maintenance 27 8 Transportation and storage 28 9 S...

Page 4: ...ks and for modifying that infor mation to change device behavior PWM pulse width modulation RTC real time clock RTD resistance temperature detectors TC thermocouple UTC Coordinated Universal Time worl...

Page 5: ...current regulations and tech nical standards 1 5 Safety WARNING Ensure the mains voltage matches the voltage marked on the nameplate Ensure the device is provided with its own power supply line and e...

Page 6: ...ur homepage akYtec de 2 1 Basic features 8 analog inputs Sect 4 8 RTD TC active linear sensors U I passive linear sensors R switch contacts supported Tab 3 2 Device and input status indicators Sect 2...

Page 7: ...cription green Off Power off On Power on Eth 1 green Off Not connected Flashing Data transfer over Ethernet 1 interface Eth 2 green Off Not connected Flashing Data transfer over Ethernet 2 interface r...

Page 8: ...6 s Linear signals 0 6 s Basic error RTD 0 25 FS TC 0 5 FS Linear signals 0 25 FS Additional error due to electromagnetic interference max 0 25 FS Temperature influence 20 of basic error 10 C Integrat...

Page 9: ...T 6651 2009 100M 0 00428 180 200 0 25 0 1 C GOST 6651 2009 500M 0 00428 180 200 0 25 0 1 C GOST 6651 2009 1000M 0 00428 180 200 0 25 0 1 C GOST 6651 2009 Ni100 0 00617 60 180 0 25 0 1 C GOST 6651 2009...

Page 10: ...g environment conditions must be observed clean dry and controlled environment low dust level closed non hazardous areas free of corrosive or flammable gases Table 3 3 Operating conditions Condition P...

Page 11: ...the device is powered over USB the inputs outputs and the Ethernet interfaces are disabled If you need full control over the device you have to connect the main power but you must observe the followin...

Page 12: ...00 To set the time click the toolbar icon Real time clock Fig 4 1 Use the button Synchronize with PC to synchronize the RTC with the PC clock Select your time zone from the drop down list below You ca...

Page 13: ...ule processor at least 2 minutes Since the number of erase cycles of the flash memory is limited it is not recommended to record the configuration parameters cyclically when the battery is low 4 4 Eth...

Page 14: ...if any have been changed are assigned to this module The address is automatically incremented by 1 for each subsequent device Only Ethernet parameters will be changed other parameters will not be aff...

Page 15: ...described in Tab 4 5 To view all logged parameters use the toolbar item Device information in akYtecToolPro The archive can be read with via Modbus TCP using function 20 Tab D 3 This function allows r...

Page 16: ...2 R AIn timestamp Timestamp of input AIn as INT16 Sect 4 8 5 0 65535 s 100 R AIn INT Measured value of input AIn as INT16 Sect 4 8 5 32768 32767 R 4 8 1 Input sampling As long as the Input signal para...

Page 17: ...n working in conditions of strong interferences it is recommended to decrease the bandwidth to eliminate their influence on the operation of the module 2 At the second stage of filtering the signal is...

Page 18: ...ond the permissible range RTD or TC sensor break RTD short circuit Cold junction temperature is beyond the range 40 90 Some transmitter errors cannot be detected Current and voltage sensor breaks The...

Page 19: ...age broker and a number of clients Broker is a server that receives all messages from the clients and then routes the messages to the appropriate des tination clients Client can be publisher or and su...

Page 20: ...for broker 0 65535 1883 RW Store last message If On other clients subscribed to the module s topics will receive the latest messages from these topics On Off Off RW Publishing interval Publishing inte...

Page 21: ...rotocol without GET requests it is recommended to set the pa rameter Safe state timeout Modbus Slave group to 0 since writing is usually event driven and not cyclic in this case Table 4 11 SNMP parame...

Page 22: ...the power supply of the module and all connect ed devices open the front cover 1 loosen the two screws 3 remove the terminal block 2 Now you can replace the device Reverse this procedure after replac...

Page 23: ...ble quick and easy replacement of the device see Fig 5 2 When wiring is completed the wires should be placed in a special recess under the cover so that adjacent devices can be placed on the DIN rail...

Page 24: ...als AIn 1 of all inputs have the same electric potential Fig 5 5 TC wiring To connect a remote thermocouple to the input use thermocouple compensating cable About using of cold junction compensation C...

Page 25: ...2 5 Switch contact Two discrete dry contact signals can be connected to each analog input switches buttons relay contacts etc Any resistors in the range 200 3000 can be used as shunt resistors Both r...

Page 26: ...o seal the unused connector with a rubber plug included Star topology The maximum length of the network lines between modules is 100 m Both Ethernet connectors can be used Fig 5 11 Star topology Chain...

Page 27: ...the factory settings all parameters but Ethernet will be reset to default values and the password deleted The Ethernet parameters will not be affected To restore the factory settings Power on the devi...

Page 28: ...power before maintenance The maintenance includes cleaning the case and terminal blocks from dust dirt and debris checking the device fastening checking the wiring connecting wires terminal connection...

Page 29: ...otection If the device is not taken immediately after delivery into operation it must be carefully stored at a protected location The device should not be stored in an atmosphere with chemically activ...

Page 30: ...kYtec GmbH Vahrenwalder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de 29 9 Scope of delivery MV210 101 1 Ethernet connection cable 1 2 pole plug in terminal block 1 Rubber pl...

Page 31: ...pendix A Dimensions akYtec GmbH Vahrenwalder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de 30 Appendix A Dimensions Fig A 1 External dimensions Fig A 2 Wall mounting dimensio...

Page 32: ...69 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de 31 Appendix B Galvanic isolation Fig B 1 Galvanic isolation The test voltages shown in Fig B 1 correspond to the tests carried out un...

Page 33: ...he module and all connected devices remove the terminal blocks without disconnecting the connected wires Fig 5 2 remove the module from the DIN rail remove the front part of the case by opening the fo...

Page 34: ...form name R 0xF020 61472 String32 Platform version R 0xF030 61488 String32 Hardware version R 0xF040 61504 String16 Additional text information R 0xF048 61512 String16 S N R 0xF084 61572 String32 MAC...

Page 35: ...0x101A 4122 REAL32 AI2 Upper measuring limit 10000 10000 RW 0x101C 4124 REAL32 AI2 Lower measuring limit 10000 10000 RW 0x101E 4126 REAL32 AI2 Filter time constant 0 65535 s RW 0x1020 4128 UINT16 AI2...

Page 36: ...RW 0x1068 4200 REAL32 AI7 Curve slope 1 10 RW 0x106A 4202 REAL32 AI7 Upper measuring limit 10000 10000 RW 0x106C 4204 REAL32 AI7 Lower measuring limit 10000 10000 RW 0x106E 4206 REAL32 AI7 Filter tim...

Page 37: ...able 0 off 1 on RW 0x1600 5632 UINT16 NTP server pool RW 0x1601 5633 String32 NTP server 1 RW 0x1641 5697 UINT32 NTP server 2 RW 0x1643 5699 UINT32 Synchronization period 5 65535 s RW 0x1645 5701 UINT...

Page 38: ...4 Modbus error codes Code Name Description 01 Illegal Function Function code received in the query is not recognized or allowed by slave 02 Illegal Data Address Data address of some or all the require...

Page 39: ...nonexistent 03 Failed to move to the desired offset in the file 04 Error while deleting file on delete request Too much data requested more than 250 bytes Invalid record number greater than 0x270F Inv...

Reviews: