Description
Values
Min
Def
Max.
A
B
C
D
E
C6
Status of COOL relay with probe fault (Page 11):
0
=OFF;
1
=ON;
2
=Average based on last 24 hours prior to probe fault;
3
=ON-OFF as prog. C7 and C8 (in heat mode always OFF)
0
0
3
No Yes Yes Yes Yes
C7
Time relay ON in case of faulty probe (Page 11):
(If C7=0 and C8
¹
0,
the relay will always be OFF deenergised)
(min.)
0
10
120
No Yes Yes Yes Yes
C8
Time relay OFF in case of fault of probe 1 (Page 11):
(If C8=0 y C7
¹
0, the relay will always be ON energised)
(min.)
0
5
120
No Yes Yes Yes Yes
C9
Maximum duration of fast freezing mode.
(
0
=off) (Pág.10)
(h.)
0
24
48
No No Yes Yes Yes
C10
Change set point (SP) in fast freezing mode, when it reaches this point
(SP + C10) returns to normal (SP+C10
³
C3)
(
0
=OFF) (Page 10)
(ºC/ºF)
0
-50
C3-SP No No Yes Yes Yes
C11
Length of inactivity at digital input to activate ECO mode
(Only if P10 or P11=1 and P0=0) (0=OFF) (Page 11)
(h.)
0
2
24
No No Yes Yes Yes
C12
Change set point (SP) in ECO mode
(SP+C12
C2) (
0
=off) (Page 11)
£
(ºC/ºF)
0
2
C2-SP No No Yes Yes Yes
EP
Exit to Level 1
Description
Values
Min
Def
Max.
A
B
C
D
E
d0
Defrost frequency (Time between two starts) (Page12)
(h.)
0
*
96
No Yes Yes Yes Yes
d1
Maximum defrost duration (
0
=defrost deactivated) Page
(
13)
(min.)
0
*
255
No Yes Yes Yes Yes
d2
Type of message during defrost: (Page 13)
0
=Current temperature;
1
=Temperature at start of defrost;
2
=Display dEF message
0
2
2
No Yes Yes Yes Yes
d3
Maximum duration of message
(time added at the end of the defrost) Page
(
13)
(min.)
0
5
255
No Yes Yes Yes Yes
d4
Defrost end temperature (probe 2) (If P4
¹
1) Page
(
13)
(ºC/ºF)
-50
8
99,9 No No Yes Yes Yes
d5
Defrost on equipment start-up
0
=NO, First defrost as per d0
1
=YES, First defrost as per d6
(Page13):
0
0
1
No No Yes Yes Yes
d6
Defrost start delay on equipment start-up (Page13)
(min.)
0
0
255
No No Yes Yes Yes
d7
Defrost type:
0
=Resistors,
1
=Inverted cycle,
(Page12)
2
=Fan / air,
3
=Compressor off
0
0
3
No No Yes Yes Yes
d8
Calculated time between defrost period (Page 13):
0
=Total actual time;
1
=Sum of times the compressor is on
0
0
1
No Yes Yes Yes Yes
Level 1.-
These parameters are visible only if the unit is in cool mode (P0=0)
Defrost Control
Level 2
Level 2
25
A:
Available in
AKO-D14012 / D14023 / D14023C / D14024
D:
Available in
AKO-D14212 / D14220 / D14223 / D14312 / D14320 / D14323 / D14323-C / D10223 / D10323
C:
Available in
AKO-D14112 / D14123-2 / D14123-2-RC
E:
Available in
AKO-D14412-RC, AKO-D14423-RC
B:
Available in
AKO-D14120 / D14123 / D14124 / D14125 / D10123