Flashing 0: Access code (Password) request
You must enter the access code configured on L5 to execute the requested
function (p. 9 and 22).
See also parameter P2 (p. 27)
Probe 1, 2 or 3 faulty
(open circuit, crossover or temperature outside the probe limits;
NTC
: -50
To 99 ºC;
PTC
:
-50 To 150 ºC).
Indicates a defrost is underway. After defrosting, the message will continue
to be displayed during the time specified in parameter d3 (see Chapter 4.2).
Alternating with temperature:
Maximum temperature in control probe alarm. Temperature set in A1 has
been reached (p. 17 and 18)
(Activates alarm relay)
Alternating with temperature:
Minimum temperature in control probe alarm. Temperature set in A2 has
been reached (p. 17 and 18)
(Activates alarm relay)
Alternating with temperature:
(Activates alarm relay)
External alarm activated (by digital input) (p. 17 and 18)
Alternating with temperature:
(by digital input) (p. 17)
(Activates alarm relay)
Severe external alarm activated
Alternating with temperature:
Defrost alarm time-out. Displayed when a defrost ends after the maximum
time elapsed as defined in parameter d1. (p. 17)
(Does not activate alarm relay)
Alternating with temperature:
Door open alarm. Shown if the door remains open longer than specified in
parameter A12 (p. 17 and 18)
(Does not activate alarm relay)
Alternating with temperature:
Pump-down time-out alarm (p. 17)
(Does not activate alarm relay)
Alternating with temperature:
Clock battery discharged or clock deprogrammed
(Does not activate alarm relay)