3.- Initial Setup
3.1.- Wizard
(not available in thermometers)
The Darwin range controllers have a setup wizard to configure the main parameters
for the type of application chosen (see table). The other parameters will be configured
according to the "Def" column in the parameter table (see section 7.1.3).
For the meaning of each parameter, see section 7.1.3.
This wizard starts the first time that the unit is powered up or at any time through the programming menu, through
P3 (see Section 7).
WARNING:
The default parameters by type of application have been defined for the most common
applications. Check that these parameters are suitable for your installation.
*Parameters not available in 3-key controllers.
DEFAULT SETTINGS BY APPLICATION (P3)
1
Multi-
purpose
2
Frozen
3
Fruits and
vegetables
4
Fresh fish
5
Soft Drinks
6
Bottle Racks
7
AC
8
Heat/
Incubators
SP
2ºC
(36ºF)
-18ºC
(-0,4ºF)
10ºC
(50ºF)
0ºC
(32ºF)
3ºC
(37,4ºF)
12ºC
(53,6ºF)
21ºC
(69,8ºF)
37ºC
(38,6ºF)
d0
4
4
4
4
24
24
96
-
d1
20
20
20
20
20
20
0
-
F0*
8ºC
(46ºF)
0ºC
(32ºF)
30ºC
(86ºF)
8ºC
(46ºF)
8ºC
(46ºF)
30ºC
(86ºF)
99ºC
(210ºF)
-
F3*
1
0
1
1
1
1
1
-
P0
0
0
0
0
0
0
0
1
7