5750H002 Ed.03
12
GAS concentr
ation (PPM)
AL6
AL8
AL5
AL6 - AL7
Alarm
ON
Alarm
OFF
Pre-
Alarm
OFF
Pre-
Alarm
ON
AL3
AL3 - AL4
Alarms
The transmitter emits an acoustic alarm, the alarm indicator flashes and activates the relays when certain gas
concentration levels are exceeded. If the transmitter is connected to a station, the station will emit the acoustic
alarm. The relays will be activated in both devices.
There are two alarm levels depending on the concentration of gas detected: Pre-Alarm and Alarm. These levels
have a factory setting of 500 and 1000 PPM respectively. These values comply with domestic and international
regulations. However, please ensure that these values comply with current local regulations. In order to modify
these values, parameter
AL1
should be configured to 1.
Pre-Alarm
Warns the user that the gas concentration is increasing.
The Pre-Alarm relay can be connected to air extraction systems to disregard possible temporary leaks or false
detections caused by external agents.
The activation level of the Pre-Alarm is determined by parameter
AL3
and is deactivated when it drops below
AL3
minus differential
AL4
.
Parameter
AL5
can be used to apply a delay period between
AL3
being exceeded and the Pre-Alarm being set off.
Parameter
AL2
can be used to disable the Pre-Alarm. Before doing this, ensure that relevant regulations permit this
action.
Alarm
Warns the user that the gas concentration has reached high levels.
It is advisable to use the alarm relay to halt installation by connecting it to the security chain.
The activation level of the Pre-Alarm is determined by parameter
AL6
and is deactivated when it drops below
AL6
minus differential
AL7
.
Parameter
AL8
can be used to apply a delay period between
AL6
being exceeded and the Alarm being set off.
Digital inputs
The transmitter has 2 digital inputs which are used to remotely activate the Mute (DI1) and Set Hold (DI2)
functions. The wiring of both is explained on page 8.
Pressing once activates or deactivates each function. The polarity of the inputs is configured using parameters
I11
(DI1) and
I21
(DI2).
Summary of Contents for AKO-575 Series
Page 1: ...AKO 575xxx Gas transmitter User manual GB 5750H002 Ed 03...
Page 26: ...5750H002 Ed 03 26...
Page 27: ...5750H002 Ed 03 27...