background image

5750H002 Ed.03

12

GAS concentr

ation (PPM)

AL6

AL8

AL5

AL6 - AL7

Alarm

ON

Alarm

OFF

Pre-

Alarm

OFF

Pre-

Alarm

ON

AL3

AL3 - AL4

Alarms

The  transmitter  emits  an  acoustic  alarm,  the  alarm  indicator  flashes  and  activates  the  relays  when  certain  gas 
concentration  levels  are  exceeded.  If  the  transmitter  is  connected  to  a  station,  the  station  will  emit  the  acoustic 
alarm. The relays will be activated in both devices.
There  are  two  alarm  levels  depending  on  the  concentration  of  gas  detected:  Pre-Alarm  and Alarm. These  levels 
have  a  factory  setting  of  500  and  1000  PPM  respectively. These  values  comply  with  domestic  and  international 
regulations.  However,  please  ensure  that  these  values  comply  with  current  local  regulations.  In  order  to  modify 
these values, parameter 

AL1 

should be configured to 1.

Pre-Alarm

Warns the user that the gas concentration is increasing.
The  Pre-Alarm  relay  can  be  connected  to  air  extraction  systems  to  disregard  possible  temporary  leaks  or  false 
detections caused by external agents.
The activation level of the Pre-Alarm is determined by parameter 

AL3

 and is deactivated when it drops below 

AL3

 

minus differential 

AL4

.

Parameter 

AL5

 can be used to apply a delay period between 

AL3

 being exceeded and the Pre-Alarm being set off.

Parameter 

AL2

 can be used to disable the Pre-Alarm. Before doing this, ensure that relevant regulations permit this 

action.

Alarm

Warns the user that the gas concentration has reached high levels.
It is advisable to use the alarm relay to halt installation by connecting it to the security chain.
The activation level of the Pre-Alarm is determined by parameter 

AL6

 and is deactivated when it drops below 

AL6

 

minus differential 

AL7

.

Parameter 

AL8

 can be used to apply a delay period between 

AL6

 being exceeded and the Alarm being set off.

Digital inputs

The  transmitter  has  2  digital  inputs  which  are  used  to  remotely  activate  the  Mute  (DI1)  and  Set  Hold  (DI2) 
functions. The wiring of both is explained on page 8.
Pressing once activates or deactivates each function. The polarity of the inputs is configured using parameters 

I11

 

(DI1) and 

I21

 (DI2).

Summary of Contents for AKO-575 Series

Page 1: ...AKO 575xxx Gas transmitter User manual GB 5750H002 Ed 03...

Page 2: ...installations incorporating our products AKO Electromec nica is not responsible for any damage caused by non compliance with regulations Follow strictly the instructions given in this manual To maxim...

Page 3: ...seen values according to the type of gas see page 3 no alarm will be activated If perimeter supervision is required several sensors should be installed around that area MODEL DESCRIPTION POWER SUPPLY...

Page 4: ...e page 11 In the programming menu it allows scrolling around the different levels or during the setting of a parameter changing its value Pressing once 1 second will show the type of gas detected the...

Page 5: ...perature of the sensor has experienced a variation of greater than 5 C during the calibration or reset to zero process See pages 21 and 22 The maximum time has been exceeded without the reading stabil...

Page 6: ...could start In compressor cooling generator rooms near to compressors and pressure accumulation tanks In this environment the elements most susceptible to refrigerant leaks are valves pressure sensor...

Page 7: ...dance Fix the glands onto the device 4 Make the 2 holes in the wall using template included Fix the unit to the wall using the screws and plugs supplied 5 If the wall is made of sheet metal prefabrica...

Page 8: ...tandards maintain that the power supply of the alarm should originate from a different circuit to that used by the refrigeration and ventilation system Please ensure that you comply with current local...

Page 9: ...larm station initiate the setup wizard in the transmitter before doing so in the station This function will not reactivate once the transmitter has been configured To reactivate the function disconnec...

Page 10: ...and o00 respectively 5 Operation Without alarms The display shows the current gas concentration in ppm Parts per million If b01 0 or the typeofgastobemeasured b01 1 Parameterb02allowsyoutofixavaluebel...

Page 11: ...nd To activate deactivate this mode press the key for 6 seconds The indicator will flash SHD SSSS If there is a sudden increase in temperature near the transmitter either in the cold room loading proc...

Page 12: ...rary leaks or false detections caused by external agents The activation level of the Pre Alarm is determined by parameter AL3 and is deactivated when it drops below AL3 minus differential AL4 Paramete...

Page 13: ...OFF Pre alarm Intermittent sound Delayed alarm Intermittent sound Alarm Bitonal sound Muted pre alarm OFF Depending on b03 Depending on b03 Muted alarm OFF Depending on b03 Depending on b03 Sensor er...

Page 14: ...ord entered is not correct the unit will go back to showing the gas concentration See page 11 Gas concentration indication Release SET to access alarm levels Release SET to access programming 3 s 6 s...

Page 15: ...g only gc2 Gas to be measured with the Universal sensor Only if Gc1 brd1 ALL 134A 404A 407A 410A 125 448A 449A 407F b01 Display 0 Measurement in PPM 1 Type of gas to be measured 0 0 1 b02 Minimum valu...

Page 16: ...ut 2 Remote Set Hold 0 Activates on opening contact 1 Activates on closing contact 0 0 1 o00 Type of output 4 20 mA Reading only 0 Calibrated for alarm station 1 Linear 0 1 EP Exit to level 1 INFORMAT...

Page 17: ...The transmitters are equipped with a port for connection of RS485 MODBUS data which allows it to remotely manage these using an AKO 5012 server The MODBUS address is set at the factory and is indicate...

Page 18: ...kit The AKO 58110 calibration kit enables the testing verification of accuracy reset to zero and calibration of the transmitter These tasks will be explained in the following pages 1 2 Install the kit...

Page 19: ...the shut off valve of the gas cylinder and wait After a few moments the transmitter concentration reading will begin to rise until it reaches the Pre Alarm and then Alarm level Check that both the Pr...

Page 20: ...the reading to stabilise Compare the reading displayed with the calibrated value of the gas cylinder If the accuracy is sufficient for the intended application it is not necessary to carry out a calib...

Page 21: ...for at least 20 minutes Install the AKO 58110 calibration kit following the instructions on page 18 Enter the programming menu by pressing the SET key for 10 seconds and access parameter 00 See page 1...

Page 22: ...s process will last for up to 15 minutes On completion if the calibration GA process has been successful the display will show End and emit a long beep Close the shut off valve of the nitrogen gas cyl...

Page 23: ...econds 300 Working life years 7 Recommended verification frequency years 1 AKO 57522 R 22 AKO 575134A R 134a AKO 575404A R 404A AKO 575410A R 410A AKO 575507A R 507A AKO 575400 Universal Alarm levels...

Page 24: ...for AKO 58110 transmitters and detectors This enables testing Bump Test verification of accuracy reset to zero and field calibration of AKO 575xxx gas transmitters AKO 58120 protector Protects the AK...

Page 25: ...plication for mobile devices this module provides the unit with multiple functionalities Data logging Activity summaries Logging of configuration changes Logging of events and alerts Remote configurat...

Page 26: ...5750H002 Ed 03 26...

Page 27: ...5750H002 Ed 03 27...

Page 28: ...etes 30 38 08812 Sant Pere de Ribes Barcelona Spain Tel 34 902 333 145 Fax 34 938 934 054 www ako com We reserve the right to supply materials that might vary slightly to those described in ourTechnic...

Reviews: