OM-229 158 Page 21
SECTION 6
−
SETUP AND OPERATION
6-1. Safety Equipment
Wear the following during
operation:
1. Dry, Insulating Gloves
2. Safety Glasses With Side
Shields
DO NOT wear rings, watches, or
other metallic items during opera-
tion.
sb3.1* 1/94
1
2
6-2. System Description
The Toccotron AC is intelligent to the point that it will automatically adjust output power levels if internal system operating parameters or internal temper-
atures reach or exceed specific set limits (see Section 9).
6-3. Power Source/System Setup
To view the System Setup screen, simultaneously press the Parameters
Hz
V
A
kW
and Program
buttons and the following screen appears on
the display:
Time Resolution: Seconds SETUP1
KW Second Alarm: No Min: 0 Max: 9999
KW Second Scale: x1 ExtInterrupt: YES
Remote Enable..: No
System Lock.: No SETUP2
Control Mode: Timed Command: Power
Max KW......: 35 Degree Units:
F
Backlight...: Yes Isolation Detect: Yes
To change a setting:
Press the Cursor
button to move the cursor to the parameter to be changed
Press Increase
or Decrease
button to select desired setup feature.
Possible selections Setup 1:
Time Resolution in seconds
−
0.1 second increments
KW Second Alarm
−
Yes/No
Minimum: 0
−
9999, Maximum: 0
−
9999
KW Second Scale
−
x1, x10, x100
External Interrupt
−
Yes/No
Remote Enable
−
Yes/No