8
ICE CEA/CGA1012–1060 Wall Mount AC I&O Manual
03/2021 Rev.1
temperature and pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred
to outdoor air drawn across the condenser by the condenser fan. Liquid refrigerant is metered into the
evaporator to repeat the cycle.
Heating Mode
A wall-mounted thermostat controls the heating cycle of models which incorporate resistance heating ele-
ments. On a call for heat, the thermostat closes the heat relay to energize the indoor fan and the resistance
elements. Except on units with the optional dehumidification kit, the compressor is locked out during the
heating cycle. Please see Appendix A for instructions on field installing electric heaters.
Economizer Operation
The economizer is a regulated damper system with controls. The damper regulates the circulation of outside
air into the enclosure (when the outdoor air conditions are suitable) to reduce the need for mechanical
cooling, save energy, and extend compressor life.
Depending upon the options selected, the damper responds to the enthalpy of the outdoor air. On a call
for cooling from a space thermostat, it operates as follows:
When the enthalpy of the outdoor air is below the set point, the outdoor air damper is proportionally open
(and return air damper is proportionally closed) to maintain between 50°F and 56°F (10°C to 13°C) at
the mixed/discharge air sensor. Integral pressure relief allows the indoor air to exit the shelter through
the air conditioner.
When the enthalpy of the outdoor air is above the set point, the outdoor air damper closes to its minimum
position. A call for cooling from the space thermostat brings on mechanical cooling.
A built-in adjustable minimum position potentiometer controls the amount of outdoor air admitted to
meet minimum ventilation requirements.
1.6
Optional Controls & Packages
Hard Start Kit
Used on single phase equipment to give the compressor higher starting torque under low voltage conditions.
Generally not recommended on units with scroll compressors.
Extreme Duty Package (not available on CEA1012)
The Extreme Duty Package allows selected ICE air conditioners to operate in extremely cold and hot
ambient conditions. The Extreme Duty Kit is always factory installed. Non-economizer air conditioners
will operate from 0° F to 131° F (-18° to 55°C). Economizer equipped air conditioners will operate from
-40° F to 131° F (-40° to 55°C).
The Extreme Duty Package includes a suction line accumulator, thermal expansion valve (TXV), crank-
case heater, hard start kit, an auto reset, high pressure switch and an outdoor thermostat and fan cycle
switch. The fan cycle control is standard on all ICE air conditioners and operates based upon the liquid
line pressure. The outside thermostat closes whenever the outside temperature is below 50°F (10°C)
and opens when the outside temperature is 50° F (10°C) or higher. Whenever the temperature is below
50°F (10°C), the fan cycle switch is in the circuit; when temperatures are 50° F (10°C) or higher, the fan
cycle switch is not in the circuit. The fan cycle control is used with a TXV to prevent excessive cycling
or "hunting" of the TXV.
Protective Coating Packages
Typically only the non-economizer air conditioners are used in corrosive environments, but units with
an economizer are also available with corrosion protection. Two corrosion protection packages are of-
fered- one for the condenser section (the Coastal Environmental package) and the other for the entire
unit (the Coat-All Package).