ICE CEA/CGA1012–1060 Wall Mount AC I&O Manual
03/2021 Rev.1
7
Note:
Follow local codes and standards when designing duct runs to deliver the required airflow.
Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and
outlet grilles in duct runs.
MODEL
0.10
0.15
0.20
0.25
0.30
0.40
0.50
CEA/CGA1012
450
420
390
360
CEA/CGA1020/1024
860
825
810
740
670
CEA/CGA1030
1100
1050
1000
960
920
810
CEA/CGA1036
1310
1265
1220
1185
1150
1060
CEA/CGA1042
1650
1585
1520
1450
1360
CEA/CGA1048
1900
1830
1760
1700
1620
CEA/CGA1060
1900
1830
1760
1700
1620
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation of units at a voltage different from the rating point
will affect air flow
.
Table 1. CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL
INCHES
MILLIMETERS
PART NUMBER
FILTERS PER
UNIT
MERV
RATING
CEA1012 (Non-Economizer)
20 x 10 x 2
508 x 254 x 52
91974
1
8
CEA1012 (With Economizer)
22¼ x 6¼ x 2
565 x 159 x 51
80172
1
8
CGA1012 (With Economizer)
12 x 25 x 1
305 x 635 x 25
93181
1
8
CEA/CGA1020/1024
25 x 16 x 2
635 x 406 x 52
80137
1
8
CEA/CGA1030/1036
30 x 16 x 2
762 x 406 x 52
80138
1
8
CEA/CGA1042/1048/1060
36½ x 22 x 2
927 x 559 x 52
80162
1
8
Table 2. Return Air Filter Sizes
MODEL
LBS
KG
Non-Economizer
CEA/CGA1012
175
79.5
CEA/CGA1020/1024
275
125
CEA/CGA1030/1036
355
160
CEA/CGA1042/1048/1060
535
245
With Economizer
CEA/CGA1012
185
84.1
CEA/CGA1020/1024
286
130
CEA/CGA1030/1036
375
170
CEA/CGA1042/1048/1060
590
268
Table 3. Shipping Weights
1.5 General Operation
Model
Ventilation Configuration
Temperature Range
Non-Economizer
Standard ("N")
20ºF – 120ºF (-7ºC – 48.9ºC)
Desert Duty ("ND")
32ºF – 130ºF (-0ºC – 54ºC)
Extreme Duty ("NE"), 60 Hz Only
0ºF – 130ºF (-18ºC – 54ºC)
With Economizer
Standard ("CE")
-40ºF – 120ºF (-40ºC – 48.9ºC)
Desert Duty ("CD")
-40ºF – 130ºF (-40ºC – 54ºC)
Extreme Duty ("CE"), 60 Hz Only
-40ºF – 130ºF (-40ºC – 54ºC)
Table 4. Ambient Temperature Operating Range
Refrigerant Cycle (Cooling Mode)
ICE CEA & CGA air conditioners use R-410A refrigerant in a conventional vapor-compression
refrigeration cycle to transfer heat from air in an enclosed space to the outside. A double blower assembly
blows indoor air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled
into gas by heat removed from the air. The warmed refrigerant gas enters the compressor where its