8
X 2450
TH 3106
COOLING PERFORMANCES
Wasted water Model X 2450 AO
NOMINAL AIR FLOW Qn : 4.500 m
3
/h
Air temperature
at evaporator inlet (°C)
Wasted water supply
BH
BS
Water temperature
°C
10
15
20
15
PT
W
20285
Water consumption
l/h 769
901
1188
PA
W
60246
Water pressure
kPa
13
18
31
21
PS
W
13493
23
15522
25
17550
27
20285
29
20285
31
20285
17
PT
W
21636
Water consumption
l/h 811
950
1252
PA
W
6092
Water pressure
kPa
14
20
35
21
PS
W
12417
23
14581
25
16745
27
18908
29
21636
31
21636
19
PT
W
23000
Water consumption
l/h 854
1000
1319
PA
W
6200
Water pressure
kPa
16
22
38
21
PS
W
9240
23
11540
25
13840
27
16140
29
18440
31
20740
21
PT
W
24412
Water consumption
l/h 903 1058 1395
PA
W
6467
Water pressure
kPa
18
25
43
23
PS
W
8045
25
10486
27
12927
29
15368
31
17810
33
20251
23
PT
W
25837
Water consumption
l/h 954 1117 1473
PA
W
6774
Water pressure
kPa
20
27
48
25
PS
W
6649
27
9233
29
11816
31
14400
33
16984
BS =Dry bulb temperature (°C)
BH =Wet bulb temperature (°C)
PT =Total cooling capacity (W)
PA =Power absorbed by the compressor
(W) (without fan motor)
PS =Sensitive cooling capacity (W)
Power absorbed by the indoor fan
= 860 W
Qn =Nominal air flow
Air output correction Qn
0,8xQn 0,9xQn
Qn
1,1xQn 1,2xQn
Total cooling capacity
0,940
0,970
1,000
1,020
1,040
Sensitive cooling capacity
0,890
0,950
1,000
1,050
1,100
Power absorbed
0,970
0,985
1,000
1,005
1,010
Working range
Mini. temperature
Maxi. temperature
Air temperature at evaporator inlet
BH (°C)
15
23
BS (°C)
21
32
Water temperature (°C)
10
34