20
INTERCONNECTIONS WITH OUTDOOR UNIT Model AR
*
VS : Standard Ventilation - FV : High Ventilation.
ELECTRICAL SPECIFICATIONS
Main power supply
Unit type
Model X 2450
Model X 3250
Power supply
3~230 V*- 50 Hz 3N~ 400 V- 50 Hz 3~230 V*- 50 Hz 3N~ 400 V- 50 Hz
Unit power
Outdoor unit
- Nominal power input
- Nominal intensity
- Maximum intensity
- Starting intensity
- Cable size
Model
Coupling
kW
A
A
A
mm
2
UC 73A
~ 230 V - 50 Hz
580
3
3,2
5
1,5
UC 73A
~ 230 V - 50 Hz
580
1,7
1,8
3
1,5
UC 103A
~ 230 V - 50 Hz
590
3,2
4
6
1,5
UC 103A
~ 230 V - 50 Hz
590
1,8
2
3
1,5
Unit type
Model X 2450
Model X 3250
Power supply
3 ~230 V* - 50 Hz
3N ~400 V - 50 Hz
3 ~230 V* - 50 Hz
3N ~400 V - 50 Hz
Models
AR
AO
AR
AO
AR
AO
AR
AO
C Ventilation(VS/FV)*
- Nominal power input
- Nominal intensity
- Maximum intensity
- Starting intensity
- Motor fuse rating
- Cable size
kW
A
A
A
A
mm
2
8,2/8,9
26/29
37/40
145/154
40
10
7,1/7,8
22/25
32/35
124/133
32/40
6/10
8,2/8,9
16/18
23/25
83/86
25
4
7,1/7,8
13/15
19/21
71/74
20/25
2,5/4
11,7/12,5
35/39
53/55
200/220
63
16
9,8/10,6
30/33
46/48
176/196
50
10
11,7/12,5
21/24
32/34
117/128
32/40
6/10
9,8/10,6
17/19
26/28
96/107
32
6
Electrical heating
- Nominal power input
- Nominal intensity
- Maximum intensity
- Starting intensity
- Motor fuse rating
- Cable size
kW
A
A
A
A
mm
2
18,7/19,3
50/53
59/62
145/154
63
16
18,7/19,3
50/53
59/62
124/133
63
16
18,7/19,3
29/31
33/35
83/86
40
10
18,7/19,3
29/31
33/35
71/74
40
10
23,4/24,3
63/74
74/76
200/220
80
25
23,4/24,3
63/74
74/76
176/196
80
25
23,4/24,3
36/43
43/45
117/128
50
10
23,4/24,3
36/43
43/45
96/107
50
10
Deshumidification
+ Ventilation (VS/F
- Nominal power input
- Nominal intensity
- Maximum intensity
- Starting intensity
- Motor fuse rating
- Cable size
kW
A
A
A
A
mm
2
26,2/26,9
73/77
91/94
199/208
100
35
25,1/25,8
70/73
86/89
178/187
100
35
26,2/26,9
43/45
53/55
113/116
63
16
25,1/25,8
40/42
49/51
101/104
50/63
10/16
34,2/35,0
94/98
120/122
267/287
125
50
32,3/33,1
89/92
113/115
243/263
125
50
34.2/35,0
55/58
71/73
156/167
80
25
32,3/33,1
52/54
65/67
135/146
80
25
+ Ventilation (VS/FV)
+ Ventilation (VS/FV)
* THREE PHASE 230 V : Installation regulated in France.
**
IMPORTANT
: These values are for information only, they should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and to the type of cables.
INTERCONNECTIONS WITH REMOTE CONTROL TRANSFORMER
INTERCONNECTION WITH REMOTE CONTROL (accessory)
Unit type
Model
X 2450
Model
X 3250
ventilation (VS/FV)
- Nominal intensity
- Maximum intensity
- Starting intensity
- Cable size
A
A
A
mm
2
1
2
3
1
TRANSFORMER (Not suppIied)
for power supply 3~400 V + Earth, without neutral
Models
AO
AR
Nominal power input
single phase transformer
400 V / 230 V in VA
X 2450
100
100
X 3250
X 2450 / X 3250
TH 3118