9
TH 3107
X 3250
COOLING PERFORMANCES
Wasted water Model X 3250 AO
NOMINAL AIR FLOW Qn : 5.800 m
3
/h
Air temperature
at evaporator inlet (°C)
Wasted water supply
BH
BS
Water temperature
°C
10
15
20
15
PT
W
28598
Water consumption
l/h 1074 1257 1658
PA
W
8113
Water pressure
kPa
14
19
33
21
PS
W
18141
23
21001
25
23861
27
26721
29
28598
31
28598
17
PT
W
30493
Water consumption
l/h 1132 1326 1748
PA
W
8218
Water pressure
kPa
16
21
37
21
PS
W
16491
23
19540
25
22589
27
25639
29
28688
31
30493
19
PT
W
32400
Water consumption
l/h 1452
1700
2242
PA
W
8370
Water pressure
kPa
26
35
61
21
PS
W
11980
23
15220
25
18460
27
21700
29
24940
31
28180
21
PT
W
34348
Water consumption
l/h 1259 1474 1944
PA
W
8706
Water pressure
kPa
19
26
46
23
PS
W
10259
25
13694
27
17129
29
20564
31
23999
33
27433
23
PT
W
36306
Water consumption
l/h 1328 1555 2050
PA
W
9090
Water pressure
kPa
21
29
51
25
PS
W
8265
27
11895
29
15526
31
19157
33
22787
BS =Dry bulb temperature (°C)
BH =Wet bulb temperature (°C)
PT =Total cooling capacity (W)
PA =Power absorbed by the compressor
(W) (without fan motor)
PS =Sensitive cooling capacity (W)
Power absorbed by the indoor fan
= 1430 W
Qn =Nominal air flow
Air output correction Qn
0,8xQn 0,9xQn
Qn
1,1xQn 1,2xQn
Total cooling capacity
0,940
0,970
1,000
1,020
1,040
Sensitive cooling capacity
0,890
0,950
1,000
1,050
1,100
Power absorbed
0,970
0,985
1,000
1,005
1,010
Working range
Mini. temperature
Maxi. temperature
Air temperature at evaporator inlet
BH (°C)
15
23
BS (°C)
21
32
Water temperature (°C)
10
34