COMPANY
‹
#
›
Error Failure Code list and Probable Cause
Indoor indicators
Outdoor indicators
Failure
Possible Reasons/Corrective actions
2* 7
segment
s
LEDs
(RUN,COOL,HEAT)
D40
D41
D42
D43
HC
HEAT OFF 3S and blink 6 times
□
■
☆
☆
PFC protection
1.PFC module assembly problem.
2.Poor heat exchange of Heatsink
3.PFC reactor problem.
4.Abnormal power voltage
5.PFC circuit problem on PCB
H7
HEAT OFF 3S and blink 7 times
□
☆
■
☆
Desynchronizing of compressor
•Abnormal power input voltage.
•Compressor wiring mistake.
•Liquid and gas valve are not open.
•EEV damaged or not proper working
•Poor heat exchange.
•Over charged system.
。
H0
HEAT OFF 3S and blink 10 times
■
□
☆
☆
HZ down due to IDU over
heating protection
1.Too high ambient temperature
2.Poor heat exchange (including blockage and bad
radiating environment )
Lc
HEAT OFF 3s and blink 11 times
□
☆
□
☆
Start-up failure
•Compressor wiring mistake
•Over charged system
•System not balanced before compressor starting
•Compressor problem
U1
HEAT OFF 3s and blink 13 times
□
☆
■
□
Malfunction of phase current
detection circuit for compressor
Phase current detection circuit for compressor has
problem.
EE
HEAT OFF 3s and blink 15 times
□
□
□
■
EEPROM failure
Replace indoor controller
PU
HEAT OFF 3S and blink 17 times
□
■
□
■
Charging malfunction of
capacitor
•Reactor open
•Charging relay or other components damaged on
PCB.
□
- LED OFF /
■
- LED ON /
☆
- LED BLINK
Summary of Contents for HDD 009
Page 1: ...AN COMPANY HDD HED Training Presentation Presented By Yossi Emquies Jan 12th 2011...
Page 5: ...AN COMPANY Specifications...
Page 6: ...AN COMPANY Out Line Dimensions Model 09 12 Indoor Unit Outdoor Unit...
Page 7: ...AN COMPANY Out Line Dimensions Model 18 24 Indoor Unit Outdoor Unit...
Page 8: ...AN COMPANY TECHNICAL ASPECTS...
Page 13: ...AN COMPANY Refrigerant Diagram Model 09...
Page 14: ...AN COMPANY Refrigerant Diagram Model 12...
Page 15: ...AN COMPANY Refrigerant Diagram Model 18...
Page 16: ...AN COMPANY Refrigerant Diagram Model 24...
Page 17: ...AN COMPANY Wiring Diagram IDU INDOOR 09 12 INDOOR 18 24...
Page 18: ...AN COMPANY Wiring Diagram ODU OUTDOOR 09 12 OUTDOOR 18 24 EEV is only for Model 24...
Page 28: ...AN COMPANY Main Control Functions...
Page 36: ...AN COMPANY Sleep Mode...
Page 37: ...AN COMPANY Clean Function and I Feel Mode Clean Function I Feel Function...
Page 42: ...AN COMPANY 9 12 Deicing Procedure Protections 18 24 models...
Page 45: ...AN COMPANY Test Mode Procedure Models 9 12...
Page 46: ...AN COMPANY Test Mode Procedure Models 18 24...
Page 47: ...AN COMPANY Forced Cooling Mode 18 24 Models Only...
Page 54: ...AN COMPANY END...