Protections
IDU Coil Overheating protection (heating mode):
During heating operation, the signals being sent from the indoor unit
allows the operation of frequency limitation in order to prevent
abnormal high pressure
.
For Model 09/12: Compressor will stop when ICT reaches 65C
For Model 18/22, Compressor will stop when ICT reaches 62C
If the unit stops as such protection for 6 times, it can not resume
running automatically and displayed an error malfunction, it can
resume by pressing ON/OFF.
IDU Freezing Protection:
During cooling operation, the signals being sent from the indoor unit allow the
operating frequency limitation and then prevent freezing of the indoor heat exchanger.
Compressor will stop when ICT <= -1 for continuous of 3 min.
If the unit stops as such protection for 6 times, it can not resume running automatically
and display malfunction, it can resume by pressing ON/OFF.
Summary of Contents for HDD 009
Page 1: ...AN COMPANY HDD HED Training Presentation Presented By Yossi Emquies Jan 12th 2011...
Page 5: ...AN COMPANY Specifications...
Page 6: ...AN COMPANY Out Line Dimensions Model 09 12 Indoor Unit Outdoor Unit...
Page 7: ...AN COMPANY Out Line Dimensions Model 18 24 Indoor Unit Outdoor Unit...
Page 8: ...AN COMPANY TECHNICAL ASPECTS...
Page 13: ...AN COMPANY Refrigerant Diagram Model 09...
Page 14: ...AN COMPANY Refrigerant Diagram Model 12...
Page 15: ...AN COMPANY Refrigerant Diagram Model 18...
Page 16: ...AN COMPANY Refrigerant Diagram Model 24...
Page 17: ...AN COMPANY Wiring Diagram IDU INDOOR 09 12 INDOOR 18 24...
Page 18: ...AN COMPANY Wiring Diagram ODU OUTDOOR 09 12 OUTDOOR 18 24 EEV is only for Model 24...
Page 28: ...AN COMPANY Main Control Functions...
Page 36: ...AN COMPANY Sleep Mode...
Page 37: ...AN COMPANY Clean Function and I Feel Mode Clean Function I Feel Function...
Page 42: ...AN COMPANY 9 12 Deicing Procedure Protections 18 24 models...
Page 45: ...AN COMPANY Test Mode Procedure Models 9 12...
Page 46: ...AN COMPANY Test Mode Procedure Models 18 24...
Page 47: ...AN COMPANY Forced Cooling Mode 18 24 Models Only...
Page 54: ...AN COMPANY END...