Compressor Target Speed Settings PI.
T
I
P
T
Load
Const
Const
*
*
int
SetPo
RoomTemp
T
Proportional
Part
Integrative
Part
Takes the effect of the
accumulated values (the history)
PI control
Room
Temperature
Set Point
Immediate response for user
set point change
Example:
Pcoeff
=20,
Icoeff
= 5
Time
∆T
Ppart
Ipart
LOAD
0
5
100
0
100
1
5
100
0+25=25
125
2
3
60
25+15=40
100
3
1
20
40+5=45
65
4
0
0
45+0=45
45
5
0
0
45+0=45
45
6
-1
-20
45-5=40
20
Summary of Contents for HDD 009
Page 1: ...AN COMPANY HDD HED Training Presentation Presented By Yossi Emquies Jan 12th 2011...
Page 5: ...AN COMPANY Specifications...
Page 6: ...AN COMPANY Out Line Dimensions Model 09 12 Indoor Unit Outdoor Unit...
Page 7: ...AN COMPANY Out Line Dimensions Model 18 24 Indoor Unit Outdoor Unit...
Page 8: ...AN COMPANY TECHNICAL ASPECTS...
Page 13: ...AN COMPANY Refrigerant Diagram Model 09...
Page 14: ...AN COMPANY Refrigerant Diagram Model 12...
Page 15: ...AN COMPANY Refrigerant Diagram Model 18...
Page 16: ...AN COMPANY Refrigerant Diagram Model 24...
Page 17: ...AN COMPANY Wiring Diagram IDU INDOOR 09 12 INDOOR 18 24...
Page 18: ...AN COMPANY Wiring Diagram ODU OUTDOOR 09 12 OUTDOOR 18 24 EEV is only for Model 24...
Page 28: ...AN COMPANY Main Control Functions...
Page 36: ...AN COMPANY Sleep Mode...
Page 37: ...AN COMPANY Clean Function and I Feel Mode Clean Function I Feel Function...
Page 42: ...AN COMPANY 9 12 Deicing Procedure Protections 18 24 models...
Page 45: ...AN COMPANY Test Mode Procedure Models 9 12...
Page 46: ...AN COMPANY Test Mode Procedure Models 18 24...
Page 47: ...AN COMPANY Forced Cooling Mode 18 24 Models Only...
Page 54: ...AN COMPANY END...