background image

8

TC5-ITA

TC5-ITA  rev.02

INSTALLATION SETUP

Po
w

e

r

Uni

t

In

le

Co
n

tro

ller

(S
la

v

e

 u

n

it)

Ai

r i

n

le

ts

Al

a

rm

In

le

Co
n

tro

ller

(P
ri

m

a

ry

 u

n

it)

In

le

Co
n

tro

ller

(S
la

v

e

 u

n

it)

In

le

Co
n

tro

lle

r

(S
la

v

e

 u

n

it)

E

n

v

ironm

en
t

Con

tro

lle

r

T

e

m

p

e

rat

ur

e

Pr
o

b

e

s

29

TC5-ITA

TC5-ITA  rev.02

Alarms - Readout

When an alarm occurs, the TC5-ITA activates the alarm contact and turns

on the alarm pilot light. The alarm readout function displays all currently

outstanding alarm situations.

Select "

ALARM READOUT

" using the function selection buttons.

The following codes can be displayed on screen:

ALARM CODE

MEAN ING

AL1

The communication between the TC 5-ITA and the 
environment controller is disrupted.

AL2

The calibration is not valid.

AL3

the temperature probe is defective or is not connected 
properly.

AL4

Low temperature alarm.

AL5

High temperature alarm.

AL6

Reception of an unprogrammed stage

NoAL

There is no active alarm.

Summary of Contents for TC5-ITA

Page 1: ...TC5 ITA Inlet Controller USER S MANUAL M 890 00047 rev 02 REV 00...

Page 2: ...ying Primary and Slave Units 13 Seasonal Programs 14 Verify TC5 ITA Operation Manual Mode 14 TC5 ITA OPERATION 15 Basic Principle of Operation 15 Calibration 18 CONTROLLER FUNCTIONS 20 Clock Settings...

Page 3: ...rev 02 Fuses at the input and outputs of the controller adequately protect its circuitry in the case of an overload or overvoltage However we rec ommend that you install an additional protection devi...

Page 4: ...ted to the TC5 ITA to centralize information management and provide monitoring and datalogging possibilities FEATURES 33 TC5 ITA rev 02 A Actuator see Inlet Alarms Conditions 29 Connection 9 Readout 2...

Page 5: ...troller is located MUST ALWAYS REMAIN BETWEEN 32o AND 104o F 0o AND 40o C For indoor use 5 TC5 ITA rev 02 LOCATION OF THE CONTROLS Status Leds DIGITAL SCREEN DISPLAY FUNCTION SELECTION BUTTONS SUB MEN...

Page 6: ...ELECTOR SWITCH IS IN THE WRONG POSITION THE DISPLAY BOARD INTERCONNECT CABLE IS UN PLUGGED FROM THE POWER SUPPLY BOARD A VARIATION IN RESISTANCE IS INDUCED ON THE SENSOR CONNECTED TO THE TC5 ITA BE SU...

Page 7: ...ting with the let ters Lo 7 TC5 ITA rev 02 INSTALLATION PROCEDURE Equipment List Integrating an air inlet control system into your ventilation system requires the following equipment A Comlink 2 commu...

Page 8: ...s on the alarm pilot light The alarm readout function displays all currently outstanding alarm situations Select ALARM READOUT using the function selection buttons The following codes can be displayed...

Page 9: ...without a temperature sensor in this case the ROOM TEMPERATURE menu will not be a available To extend the probe This probe can be extended up to 500 ft 150 m Use a shielded cable of outside diameter b...

Page 10: ...es jumper JP5 and the computer line uses JP4 Use pins 2 and 3 for YES and pins 1 and 2 for NO The following diagram shows a typical connection with the appro priate jumper configurations END OF LINE J...

Page 11: ...e adjustment buttons to set the hour to the desired value Press the right arrow key once The minutes flash on the display Use the adjustment buttons to set the minutes to the desired value Press the r...

Page 12: ...t is required to fully open close the inlet panel in order to reset the inlet position The reset delay of an inlet must be greater than its total opening time This ensures the inlet panel to be comple...

Page 13: ...e opening of the panel Set internal switch 8 to ON to use this reset method This resetting method requires the pres ence of limit switches at both ends of the actuator ON OFF ON OFF 13 TC5 ITA TC5 ITA...

Page 14: ...he air inlet then put a limit switch at this position to prevent the actuator from opening any further ON OFF 23 TC5 ITA TC5 ITA rev 02 The cummulative opening times of an air inlet cannot ex ceed the...

Page 15: ...row key to select the next step Use the adjustment buttons to specify the opening time that needs to be added to the previous opening or to specify the inlet opening in associated with the selected st...

Page 16: ...diate step is enabled the inlet opens during half the variable stage s opening when the stage s speed is of 75 it reaches the stage s HI opening position when the fan speed is 100 The three following...

Page 17: ...STALLATION PROCEDURE chapter To display the identification number Select IDENTIFICATION NUMBER using the function selection buttons The identification number is displayed alternating with ID and PRI o...

Page 18: ...you want to program with internal switch 3 19 TC5 ITA TC5 ITA rev 02 CALIBRATION SETTINGS 1 Select CALIBRATION using the function selection buttons 2 Press and hold the right arrow key for 2 seconds o...

Page 19: ...you want to program with internal switch 3 19 TC5 ITA TC5 ITA rev 02 CALIBRATION SETTINGS 1 Select CALIBRATION using the function selection buttons 2 Press and hold the right arrow key for 2 seconds o...

Page 20: ...STALLATION PROCEDURE chapter To display the identification number Select IDENTIFICATION NUMBER using the function selection buttons The identification number is displayed alternating with ID and PRI o...

Page 21: ...diate step is enabled the inlet opens during half the variable stage s opening when the stage s speed is of 75 it reaches the stage s HI opening position when the fan speed is 100 The three following...

Page 22: ...row key to select the next step Use the adjustment buttons to specify the opening time that needs to be added to the previous opening or to specify the inlet opening in associated with the selected st...

Page 23: ...he air inlet then put a limit switch at this position to prevent the actuator from opening any further ON OFF 23 TC5 ITA TC5 ITA rev 02 The cummulative opening times of an air inlet cannot ex ceed the...

Page 24: ...e opening of the panel Set internal switch 8 to ON to use this reset method This resetting method requires the pres ence of limit switches at both ends of the actuator ON OFF ON OFF 13 TC5 ITA TC5 ITA...

Page 25: ...t is required to fully open close the inlet panel in order to reset the inlet position The reset delay of an inlet must be greater than its total opening time This ensures the inlet panel to be comple...

Page 26: ...e adjustment buttons to set the hour to the desired value Press the right arrow key once The minutes flash on the display Use the adjustment buttons to set the minutes to the desired value Press the r...

Page 27: ...es jumper JP5 and the computer line uses JP4 Use pins 2 and 3 for YES and pins 1 and 2 for NO The following diagram shows a typical connection with the appro priate jumper configurations END OF LINE J...

Page 28: ...without a temperature sensor in this case the ROOM TEMPERATURE menu will not be a available To extend the probe This probe can be extended up to 500 ft 150 m Use a shielded cable of outside diameter b...

Page 29: ...s on the alarm pilot light The alarm readout function displays all currently outstanding alarm situations Select ALARM READOUT using the function selection buttons The following codes can be displayed...

Page 30: ...ting with the let ters Lo 7 TC5 ITA rev 02 INSTALLATION PROCEDURE Equipment List Integrating an air inlet control system into your ventilation system requires the following equipment A Comlink 2 commu...

Page 31: ...ELECTOR SWITCH IS IN THE WRONG POSITION THE DISPLAY BOARD INTERCONNECT CABLE IS UN PLUGGED FROM THE POWER SUPPLY BOARD A VARIATION IN RESISTANCE IS INDUCED ON THE SENSOR CONNECTED TO THE TC5 ITA BE SU...

Page 32: ...troller is located MUST ALWAYS REMAIN BETWEEN 32o AND 104o F 0o AND 40o C For indoor use 5 TC5 ITA rev 02 LOCATION OF THE CONTROLS Status Leds DIGITAL SCREEN DISPLAY FUNCTION SELECTION BUTTONS SUB MEN...

Page 33: ...ted to the TC5 ITA to centralize information management and provide monitoring and datalogging possibilities FEATURES 33 TC5 ITA rev 02 A Actuator see Inlet Alarms Conditions 29 Connection 9 Readout 2...

Page 34: ...rev 02 Fuses at the input and outputs of the controller adequately protect its circuitry in the case of an overload or overvoltage However we rec ommend that you install an additional protection devi...

Page 35: ...ying Primary and Slave Units 13 Seasonal Programs 14 Verify TC5 ITA Operation Manual Mode 14 TC5 ITA OPERATION 15 Basic Principle of Operation 15 Calibration 18 CONTROLLER FUNCTIONS 20 Clock Settings...

Page 36: ...TC5 ITA Inlet Controller USER S MANUAL M 890 00047 rev 02 REV 00...

Reviews: