12
TC5-ITA
TC5-ITA rev.02
Comlink-2 Location & Connection
a. Unplug each unit.
b. Plug the communication card in the unit.
Open the cover. Drill a 5/16" hole through the bottom of the controller and
thread the communication cable through the hole. Use the grommet pro-
vided to secure the cable. Connect the cable to the terminals of the com-
munication card as shown below. When connecting two cable ends to-
gether, solder the joint and use a heat shrink to ensure a proper contact.
Line-up the comlink card with the con-
nector and insert it in the upright posi-
tion (see illustration beside). For com-
munication, always use a 1 twisted pair
shielded cable. The maximum length of
the cable is 3000m and the recom-
mended wire diameter is 1.0 mm. Use
a lightning protection module when
running the cable between buildings.
COMLINK-2 CARD
25
TC5-ITA
TC5-ITA rev.02
Adjust the Reset Delay:
This is the delay that is required to fully open / close the inlet panel in order
to reset the inlet position. The reset delay of an inlet must be greater than
its total opening time. This ensures the inlet panel to be completely opened
or closed while its position is being reset.
The Reset Delay can be adjusted from 60 to 900 seconds in increments of
15 seconds.
•
Select "
RESET SETTINGS
" using the function selection buttons.
•
Press the right-arrow key until the Reset Delay is displayed alter-
nating with letters
"dEL".
•
Use the adjustment buttons to set the
Reset Delay
to the desired
value.
•
Proceed in similar fashion to set the Reset Delay on all
TC5-ITA units.
Manual & Automatic Resets
The reset of an inlet can either be performed manually (which is useful
when the user detects an offset in the inlet position) and/or it can be per-
formed at regular intervals (auto-reset).
Manual Reset:
To perform a manual reset, switch internal switch #9
from OFF to ON.
Automatic Reset:
Set internal switch #7 to ON to enable the auto-
reset function then program the auto-reset settings
as explained in the following section.
ON
OFF
ON
OFF