14
TC5-ITA
TC5-ITA rev.02
Seasonal Programs
All controller parameters can be set separately for winter and for summer
seasons. Select the proper season using internal switch #3 :
ON
= Winter
OFF =
Summer
Make sure to select the right season is selected before
making changes to the parameters.
Verify TC5-ITA Operation (Manual Mode)
•
Power the TC5-ITA then select MANUAL MODE using the func-
tion selection buttons.
•
Use the adjustment buttons to select the desired actuator status:
select
"OPEn"
to open,
"CLoS"
to close or
"OFF"
to stop the actua-
tor. The manual mode's status LED turns on when the actuator is
controlled manually.
VERIFY THE MOTOR'S OPERATION:
•
Manually open or close the air inlet panels as explained above. The
air inlet panels should open when the "
OPEn
" option is selected and
should close when the "
CLoS
" option is selected. If the air inlet
panels move the opposite way, the motor operates in the wrong
direction. Turn off the power and reverse the wires connected to the
actuator's open and close terminals. Verify that the motor now oper-
ates in the right direction.
VERIFY LIMIT POSITIONS OF AIR INLET PANELS:
•
Select "
CLoS
" to fully close the air inlet then put the actuator's
limit switch at this position to prevent it from closing any further;
select "
OPEn
" to fully open the air inlet then put a limit switch at
this position to prevent the actuator from opening any further.
ON
OFF
23
TC5-ITA
TC5-ITA rev.02
The cummulative opening times of an air inlet cannot ex-
ceed the inlet's
Total Opening Time
parameter value.
If the opening of the air inlet is set as a percentage, the
controller may have to sligthly adjust the inlet opening val-
ues due to some internal restriction in the conversion pro-
cess.
SELECTING THE NUMBER OF INTERMEDIATE OPENING STEPS
Follow this procedure to select the number intermediate opening steps
that are performed during variable stages (see BASIC PRINCIPLE OF
OPERATION chapter for further information).
•
Select "
REMAINING RUN TIME / OPENING"
using the function se-
lection buttons.
•
Press and hold the right-arrow key for 2 seconds. The number of
intermediate steps flashes, alternating with the letters "
NbS
" and
"
StEP
.
•
Use the adjustment buttons to set the number of intermediate steps
to the desired value. This value ranges from 0 to 2 steps.
Remaining Run Time / Opening Menu
If the inlet opening is displayed as a time value (internal switch #11 is OFF),
the REMAINING RUN TIME / OPENING menu shows a countdown of the
remaining moving time of the air inlet (opening or closing time). A negative
value is displayed when the inlet is closing. The letters "STOP" are dis-
played if the inlet is not moving.
If the inlet opening is displayed as a percentage, the REMAINING RUN
TIME / OPENING menu shows the current opening (in %) of the air inlet.