Airstream INTER 2V4SA User Manual Download Page 9

32

INTER 2V4SA, rev.02

INTER 2V4SA

Outside T° Compensation

on High T° Alarms

Outside

Temp.

Time

Room 

Alarm 

Limit

Set 

Point

Normal temperature range (no alarm)
Alarm : temperature out of range

Hi Offset

Lo Offset

11.3.  Alarm Settings

11.3.1. Hi/Lo Alarm Offsets & Criti-
cal Alarm

Hi  &  lo  alarm  offsets  range  from  0,3  to 
20,0°C  (0,5°F  to  36,0°F)  and  the  critical 
alarm limit ranges from the high alarm limit 
to 49,0°C (120,0°F).

• Select the 

ALARMS 

menu. The low alarm 

offset flashes on the display, alternating with 
the word "

Lo AL

". Use the adjustment buttons 

to set it to the desired value.

• Press the Other Functions button. The high 
alarm offset flashes on the display, alternating 
with the word "

HI AL

". Use the adjustment 

buttons to set it to the desired value.

• Press the Other Functions button. The alarm 
type "

TyPE

" is displayed, alternating with the 

word "

ALL

" or "

Ind

".

• Use the adjustment buttons to select de-
sired option :  

•  Select  "ALL"  for  temperature  alarms  to 
sound  when  the  average  temperature  of 
all  probes  exceeds  the  normal  temperature 
range; Select "Ind" for temperature alarms to 
sound when the temperature of an individual 
probe exceeds the limits.

• Press the Other Functions button. The criti-
cal alarm limit is displayed, alternating with 
the word "

Cr AL"

. Use the adjustment buttons 

to set it to the desired value.

11.3.2. Outside Temp. Alarm Offset

The outside temperature alarm offset deter-
mines when an alarm sets off when the room 
temperature  gets  higher  than  the  outside 
temperature. This parameter ranges from 0,3 
to 20,0°C (0,5°F to 36,0°F).

• Select the 

OUTSIDE TEMP./OFFSET 

menu. 

The current outside temperature is displayed. 
The letter "P" is displayed if no probe is con-
nected to the outside temperature input.

• Press the Other Functions button. The out-
side temperature alarm offset flashes on the 
display, alternating with the word "

OFSEt".

•  Use the adjustment buttons to set it to the 
desired value.

9

INTER 2V4SA, rev.02

INTER 2V4SA

4.4.  Temperature Probes

The controller is supplied with one tempera-
ture probe connected to input #1. Up to three 
additional  probes  can  be  connected  to  the 
controller in order to obtain a more accurate 
reading of the average room temperature and 
a faster reaction time.

I.  Connecting the Probes

•  Connect  additional  probes  to 
inputs # 2, 3 and 4 as shown on 
the wiring diagram and then use 
dipswitches  3-5  to  enable  the 
proper inputs:

#

OFF

ON

3

Probe 2 disabled

Probe 2 enabled

4

Probe 3 disabled

Probe 3 enabled

5

Probe 4 disabled

Probe 4 enabled

II.  Extending the Probes

Probes operate at low voltage and are 
isolated from the supply.  Be sure that 
probe cables remain insulated from all 
high voltage sources. In particular, do 
not route the probe cables through the 
same electrical knockout as other cables. 
Do not connect the shield from the probe 
cable to a terminal or a ground.

Extending a probe:

  Each probe can be ex-

tended up to 500 feet (150 meters). 

To extend a probe: Use a shielded cable of 
outside diameter between 0.245 and 0.260 
in (6.22 and 6.60 mm) (the cable dimensions 
should not be under 18 AWG) to ensure the 
cable  entry  is  liquid  tight.   

Do  not  ground 

the shielding.

It  is  preferable  to  solder  the  cable  joint  to 
ensure  a  proper  contact  between  the  two 
cables.

ON

OFF

Do not run probe cables next to other 
power cables. When crossing over other 
cables, cross at 90°.

III.  Defective Probes

If a defective probe is detected, the Defective 
Probe Pilot Light turns on. The room tempera-
ture shown on the display corresponds to the 
average temperature measured by the probes 
in working condition.

To identify the defective probe:

• Select the 

PROBE TEMP / MIN / MAX 

menu.

 

If  the  probe  connected  to  input  #  1  is  not 
defective,  the  letters  "

PR1

"  are  displayed, 

alternating with the on/off state of the probe 
and the temperature measured by the probe. 
If the probe is defective, the letters "

PR1

" are 

displayed, alternating with the state of the 
probe and the letter "

P

".

• Press the Other Functions button to step 
to the following probe.

• Proceed as explained above to make sure 
all probes are in working order.

Summary of Contents for INTER 2V4SA

Page 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Page 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Reviews: