8. 

Minimum Ventilation 

Cycles

8.1.  Principle of Operation

Definition:

  Minimum  ventilation  cycles  are 

activated  when  the  room  temperature  is 
lower than the set point. Running the fans 
even  though  ventilation  is  not  required  for 
reducing the room temperature is useful to 
reduce  humidity  levels  and  supply  oxygen 
to the room. It also prevents the fans from 
freezing in winter.

Minimum  Ventilation  Timer: 

During  the  

"On Time"

,  the  fans  of  stage  1  run  at  their 

minimum speed and Stage 1 status LED is 
on;  during  the 

"Off  Time"

,  the  fans  return 

to a stop and the status LED switches off. 
Note that the minimum speed of stage 1 can 
automatically be adjusted over time with a 
ramp (see below).

 

Min.Vent

Status

ON

OFF

Time

On Time

Off

Time

Minimum 

Ventilation Timer

The controller supplies maximum voltage 
to the variable-speed fans for 2 seconds 
at each start-up.

8.2.  Minimum Ventilation 

Timer Settings

The On and Off Times of the minimum ventila-
tion timer can be adjusted between 0 and 900 
seconds, in increments of 15 seconds.

To run the fans continuously at minimum 
speed, set the Off Time to zero and On 
Time to any value other than zero.

To stop the fans, set the On Time to 
zero and Off Time to any value.

To run the fans intermittently, set the 
On Time to the desired running time and 
Off Time to the desired off time.

• Select the 

STAGE 1 BANDWIDTH/TIMER 

menu. 

•  Press  the  Other  Functions  button.  The 
On  Time  of  stage  1  flashes  on  the  display 
"

t. On

".

• Use the adjustment buttons to set it to the 
desired value. 

•  Press  the  Other  Functions  button.  The 
Off Time of stage 1 flashes on the display 
"

t. Off

".

• Use the adjustment buttons to set it to the 
desired value. 

19

INTER 2V4SA, rev.02

INTER 2V4SA

7.1.2.  De-icing of Stage 2 Fans

Stage  2  fans  can  automatically  be  de-iced 
in cold weather conditions. When a de-icing 
cycle starts, Stage 1 fans are stopped then 
stage 2 fans start running at full speed for 
2  seconds.  Stage  2  fans  then  run  at  the 
minimum speed of stage 2 during the de-icing 
time.  Once  the  de-icing  time  has  elapsed, 
stage 2 fans stop and the operation of stage 
1 is resumed. Set internal switch #11 to ON 
to enable the de-icing function.

De-icing

Status

ON

OFF

Time

De-icing

time

Cycle 

Time

De-icing Timer

Summary of Contents for INTER 2V4SA

Page 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Page 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Reviews: