Airstream INTER 2V4SA User Manual Download Page 30

30

INTER 2V4SA, rev.02

INTER 2V4SA

10.3.  Heater Settings

I.  Adjusting Heater Offsets

The  heater  offset  can  provide  substantial 
energy savings if correctly adjusted accord-
ing to the outside temperature. This offset 
represents the number of degrees below the 
set point at which the heating units turn off 
(see diagram above). The offset of heaters 1 
and 2 can be adjusted from -5,0

°

C to 10,0°C 

(-9,0°F to 18,0

o

F). If the offset is negative, 

the heating units will turn off at temperatures 
above  the  set  point.  If  the  controller  uses 
cascade heaters , only Heater 1 offset has 
to be set.

 • Select the 

HEATER 1 OFFSET/DIFFEREN-

TIAL 

or

 HEATER 2 OFFSET/DIFFERENTIAL

 

menu. The current heater offset is displayed, 
alternating with the letters "

OF.SET

".

• Use the adjustment buttons to set it to the 
desired value.

II.  Adjusting Heater Differentials

The  heating  differential  is  the  temperature 
difference  between  the  moment  the  heat-
ing units turn on and the moment they turn 
off (see diagram above). It can be adjusted 
between  0,3°C  and  10,0°C  (0,5°F  and 
18,0°F).

• Select the 

HEATER 1 OFFSET/DIFFEREN-

TIAL 

or

 HEATER 2 OFFSET/DIFFERENTIAL

 

menu.

•  Press  the  Other  Functions  button.  The 
differential is displayed, alternating with the 
letters "

dIF

".

• Use the adjustment buttons to set it to the 
desired value.

III.  Adjusting  the  Max.  T°  Differ-

ence Between Zones

When using zoned heating, a built-in protec-
tion  will  operate  the  fans  according  to  the 
zone  1  probes  whenever  the  temperature 
difference between zones is greater than this 
parameter. The default value is 4,0°C (7,2°F) 
and  values  range  from  0,3  °C  to  20,0°C 
(0,5°F to 36,0°F).

• Select the 

HEATER 2 — OFFSET/DIFFER-

ENTIAL 

menu.

 

• Press the Other Functions button twice. The 
maximum  temperature  difference  between 
zones is displayed, alternating with the let-
ters "

Zn diF.

".

•  Use  the  adjustment  buttons  to  set  this 
parameter to the desired value.

11

INTER 2V4SA, rev.02

INTER 2V4SA

6. 

Temperature Settings

6.1.  Temperature Units

To select the desired measuring units used 
to display temperatures, set internal switch 
# 2 to the desired position:

ON:

 to display temperatures in 

Celsius units.

OFF:

 to display temperatures in 

Fahrenheit units.

6.2.  Viewing Temperatures

I.  Viewing the Room Temperature

The room temperature is the average value 
of  all  temperatures  measured  by  activated 
probes in proper operating condition.

• Select the 

ROOM TEMP MIN / MAX 

menu. 

The average room temperature is displayed.

II.  Viewing Probe Temperatures

The controller can display probe temperatures 
individually. Probes can also be turned on or 
off  to control the temperature in different 
parts of the building. 

•  Select  the 

PROBE  TEMP  /  MIN  /  MAX 

menu. The temperature reading of probe 1 
is displayed, alternating with letters "

Pr 1

and the on/off state of the probe.

• Press the Other Functions button. The let-
ters "

Pr 1

" are displayed, alternating with the 

temperature reading from probe 1 and the on/
off state of the probe.

• For each additional probe, Other Functions 
button. The letters "

Pr x

" are displayed, al-

ternating with the temperature reading from 
probe x and the on/off state of the probe.

2

ON

OFF

ON

OFF

2

III.  Viewing  Minimum  /  Maximum 

Temperatures

Follow this procedure to see the lowest and 
highest room temperature values that have 
been recorded since the last reset. 

• Select the 

ROOM TEMP MIN / MAX 

menu. 

The average room temperature is displayed.

• Press the up-arrow adjustment button.  The 
maximum temperature is displayed, alternat-
ing with the letters "

Hi

".

• Press the down-arrow adjustment button. 
The average temperature is displayed.  Press 
the  down-arrow  adjustment  button  once 
again.    The  minimum  temperature  is  dis-
played, alternating with the letters "

Lo

".

NOTE

: If you let the display flash for more 

than 10 seconds, the controller resets the min 
and max temperatures currently in memory 
to the current average room temperature. To 
avoid  resetting  these  values,  return  to  the 
average temperature display using the adjust-
ment button (up-arrow or down-arrow) before 
the 10 second delay has elapsed.

IV.  Viewing  Min/Max  Probe  Tem-

peratures

Follow this procedure to see the lowest and 
highest temperature readings that have been 
recorded by each probe since the last reset. 

•  Select  the 

PROBE  TEMP  /  MIN  /  MAX 

menu. The temperature reading of probe 1 is 
displayed, alternating with the letters "

Pr 1

and the on/off state of the probe.

• Press the up-arrow adjustment button. The 
maximum temperature of probe1 is displayed, 
alternating with the letters "

Pr1 Hi

".

• Press the down-arrow adjustment button. 
The  current  temperature  of  probe  1  is  dis-
played once again.

Summary of Contents for INTER 2V4SA

Page 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Page 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Reviews: