Airstream INTER 2V4SA User Manual Download Page 18

18

INTER 2V4SA, rev.02

INTER 2V4SA

Merge between Stages 1 and 2

(with negative Stage 2 Offset)

100%

Stage1 Override

Min speed 

 Stage 1 

Min speed 

100%

Variable 

Stage 2 speed

Variable 

Stage 1 speed

Off

 Stage 2

Min speed 

Off

Room T°

Room T°

Stage 2 

Bandwidth

Stage 1 Bandwidth

Stage 1 Bandwidth

Stage 2 

Bandwidth

S2 Offset

S2 Offset

23

INTER 2V4SA, rev.02

INTER 2V4SA

8.3.  RH Compensation on 

the Min. Ventilation 

Speed

The minimum speed of stage 1 can automati-
cally be adjusted as a function of relative hu-
midity.  As  humidity  increases,  the  minimum 
speed increases proportionally to compensate 
for the change. At humidity levels at or below 
the humidity set point, the minimum speed is 
equal  to  the  normal  uncompensated  speed. 
The user specifies the percentage increase in 
minimum speed for a relative humidity equal to 
the humidity set point + 10%. For example, if 
the minimum speed is 40% and the compensa-
tion adjustment is 30%, the minimum speed 
will  be  adjusted  to  70%  of  full  speed  when 
the  humidity  rises  10%  above  the  humidity 
set point. In addition to adjusting the minimum 
speed,  the  humidity  compensation  feature 
also  changes  the  operation  of  the  minimum 
ventilation cycle:  if the controller is operating 
in minimum ventilation mode when the relative 
humidity exceeds the humidity set point, the 
minimum ventilation fans are operated continu-
ously rather than cycled.

RH Comp. on the Min 

Ventilation Speed

RH Level

(%)

10%

RH Set Point

Compensat-

ed speed

Regular 

speed

Min. Vent.

speed of 

stage 1

When  a  compensation  is  applied  on  the 
minimum speed, the "Compensation" status 
LED turns on.  

I.  Viewing  the  Relative  Humidity 

Level (%)

•  Select  the 

RELATIVE  HUMIDITY  MIN/

MAX 

menu.  The  current  relative  humidity 

is displayed. 

• Press the up-arrow adjustment button.  The 
maximum  humidity  flashes  on  the  display, 
alternating with the letters "

rH Hi

".

•  Press  the  down-arrow  adjustment  but-
ton. The relative humidity is displayed once 
again.    Press  the  down-arrow  adjustment 
button once again.  The minimum humidity 
flashes on the display, alternating with the 
letters "

rH Lo

".

 

If  you  let  the  display  flash  for  more 
than  10  seconds  when  the  maximum 
or  minimum  humidity  is  displayed, 
the controller resets the minimum and 
maximum humidity values currently in 
memory (the display stops flashing to 
indicate that the reset has been done).

II.  Adjusting the Relative Humidity 

Set Point

When  the  relative  humidity  level  exceeds 
the humidity set point, the minimum speed 
of stage 1 starts increasing in linear fashion 
proportionally to the humidity level to com-
pensate.  

• Select the 

STAGE 1 RH COMPENSATION 

menu. The relative humidity set point is dis-
played  alternating with the letters "

Set

".

• Use the adjustment buttons to set it to the 
desired value. 

Summary of Contents for INTER 2V4SA

Page 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Page 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Reviews: