Airstream INTER 2V4SA User Manual Download Page 24

24

INTER 2V4SA, rev.02

INTER 2V4SA

III.  Adjusting  the  Compensation 

Speed

This is the percentage of increase in minimum 
speed  for  a  relative  humidity  equal  to  the 
humidity set point + 10%.  The value ranges 
from 0 to 100%.

• Select the 

STAGE 1 RH COMPENSATION 

menu. 

•  Press  the  Other  Functions  button.  The 
minimum speed compensation is displayed, 
alternating with the letters "

SPEEd

". 

• Use the adjustment buttons to set it to the 
desired value. 

IV.  Activating/Deactivating  Humid-

ity Compensation

• Select the 

STAGE 1 RH COMPENSATION 

menu. 

• Press the Other Functions button twice. The 
current on/off state of humidity compensa-
tion flashes on the display.

• Use the adjustment buttons to enable or 
disable this function.

8.4.  Minimum Ventilation 

Speed Ramp

The controller can automatically adjust the 
minimum ventilation speed of stage 1 fans 
with time. The minimum ventilation curve is 
composed of 10 steps and each step associ-
ates a speed with a day number. Once the 
curve is enabled, the controller changes the 
minimum ventilation speed of stage 1 fans 
every hour in a linear fashion between con-
secutive steps of the curve. When it reaches 
the last step, the controller keeps using the 
last  minimum  ventilation  speed  associated 
with that day.

Speed 10

Speed 9

Speed 8

Speed 7

Speed 6

Speed 5

Speed 4

Speed 3

Speed 2

Speed 1

Min. Ventilation

Ramp

1  2  3  4  5  6  7  8  10 11  12 

 DAYS 

 Min.Vent

 Speed 

(stage 1)

Notes: 

Certain  restrictions  apply  to  reduce 

the risk of errors: 

i)  Decreasing  minimum  speeds  are  not  al-
lowed.

ii) All ten steps must be specified. If you don’t 
need 10 different steps, repeat the last mini-
mum speed for each unnecessary step.

iii) The minimum speed ramp must be deac-
tivated  before  specifying  the  steps  on  the 
ramp (see below).

iv) The min. speed variation cannot exceed 
10% per day.

17

INTER 2V4SA, rev.02

INTER 2V4SA

7.1.1.   Merging Fan Stages 1 & 2

The transition from Stage 1 to Stage 2 can 
create jumps in the volume of displaced air. 
To prevent this, Stage 1 fans automatically go 
to their Override Minimum Speed when stage 
2 starts. As the room temperature increases, 

fan Stages 1 & 2 both increase in speed to 
create a smooth progression and both reach 
their maximum speed at the end of Stage 2 
Bandwidth. Refer to 7.2 on page 20 to set the 
Override Minimum Speed for stage 1.

Merge between Stages 1 and 2

(with positive Stage 2 Offset)

100%

Stage1 Override

Min speed 

 Stage 1 

Min speed 

100%

Variable 

Stage 2 speed

Variable 

Stage 1 speed

Off

 Stage 2

Min speed 

Off

Room T°

Room T°

 Set Point

Stage 1 Bandwidth

Stage 2 Bandwidth

Stage 2 Bandwidth

S2 Offset

S2 Offset

Stage 1 Bandwidth

 Set Point

Summary of Contents for INTER 2V4SA

Page 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Page 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Page 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Page 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Page 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Page 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Page 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Page 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Page 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Page 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Page 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Page 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Page 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Page 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Page 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Page 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Page 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Page 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Page 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Page 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Page 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Reviews: