background image

En-4

Do not use copper pipes that have a collapsed, deformed, or discolored portion 
(especially on the interior surface). Otherwise, the expansion valve or capillary tube 
may become blocked with contaminants.

Improper pipe selection will degrade performance. As an air conditioner using R410A 
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary 
to choose adequate materials.

•  Thicknesses of copper pipes used with R410A are as shown in the table.
•  Never use copper pipes thinner than those indicated in the table even if they are 

available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [in. (mm)]

Thickness [in. (mm)]

1/4 (6.35)

0.032 (0.80)

3/8 (9.52)

0.032 (0.80)

1/2 (12.70)

0.032 (0.80)

5/8 (15.88)

0.039 (1.00)

3/4 (19.05)

0.047 (1.20)

4.2. Pipe requirement

 CAUTION

Refer to the installation manual for the outdoor unit for description of allowable pipe 
length and height difference.

Use pipe with water-resistant heat insulation.

 CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may 
cause water leaks. 
Use heat insulation with heat resistance above 248 °F (120 °C). (Reverse cycle model 
only) 
In addition, if the humidity level at the installation location of the refrigerant piping is 
expected to exceed 70 %, install heat insulation around the refrigerant piping. 
If the expected humidity level is 70-80 %, use heat insulation that is 19/32 in. 
(15 mm) or thicker and if the expected humidity exceeds 80 %, use heat insulation 
that is 25/32 in. (20 mm) or thicker. If heat insulation is used that is not as thick as 
speci

fi

 ed, condensation may form on the surface of the insulation. 

In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less 
(at 68 °F (20 °C)).

1

4.3.  Flare connection (pipe connection)

4.3.1. Flaring

Use special 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert 

the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor and outdoor units 

respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use 

the special R410A 

fl

 are tool. Leakage of refrigerant may result if other 

fl

 are nuts are 

used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Check if [L] is 

fl

 ared uniformly and 

is not cracked or scratched.

Die

Pipe

A

B

L

Pipe outside diameter 

[in. (mm)]

Dimension A [in. (mm)]

                                      

0 (0)

Dimension B

-0.015 (-0.4) 

[in. (mm)]

Flare tool for R410A, 

clutch type

1/4 (6.35)

0 to 0.020 

(0 to 0.5)

11/32 (9.1)

3/8 (9.52)

17/32 (13.2)

1/2 (12.70)

21/32 (16.6)

5/8 (15.88)

25/32 (19.7)

3/4 (19.05)

15/16 (24.0)

When using conventional (R22) 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should 

be approximately 0.020 in. (0.5 mm) more than indicated in the table (for 

fl

 aring with 

R410A 

fl

 are tools) to achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the 

dimension A. It is recommended that a R410A 

fl

 aring tool is used.

Pipe outside

diameter [in. (mm)]

Width across flats

of Flare nut [in. (mm)]

1/4 (6.35)

21/32 (17)

3/8 (9.52)

7/8 (22)

1/2 (12.70)

1-1/32 (26)

5/8 (15.88)

1-5/32 (29)

3/4 (19.05)

1-13/32 (36)

3.3.3. Attach the drain hose

 CAUTION

Insert the drain hose and drain cap into the drain port, making sure that it comes 
in contact with the back of the drain port, and then mount it. If the drain hose is not 
connected properly, leaking will occur.

•  Wrap the insulation around the drain hose, making sure that there are no gaps.
•  Attach the Insulation (Drain hose) to the drain hose.

Drain hose

Insulation (Drain hose)
(Accessories)

[For 

1

 Rear piping, 

2

 Right piping and 

3

 Bottom piping]

•  The drain hose and drain cap are used as they are.

[For 

4

 Left bottom piping, 

5

 Left piping and 

6

 Center piping, 

7

 Left rear piping]

•  Remove the drain cap and drain hose. Mount the drain cap and drain hose to the drain 

port on its opposite side. 

Left side

Right side

Drain cap

Drain hose

Drain cap

Drain hose

Insert the drain hose until it butts 
against the drain port.

Insert the drain cap until it butts 
against the drain port.

3.3.4. Cut-out for piping on front cover

[For 

2

 Right piping, 

3

 Bottom piping, 

4

 Left bottom piping and 

5

 Left piping]

•  Use a metal shears or other cutting tool to cut along the groove in the plastic for the 

piping that will coming out of the front cover.

For 

2

 Right piping

For 

5

 Left piping

For 

4

 Left bottom piping

For 

3

 Bottom piping

4. PIPE INSTALLATION

]

 CAUTION

Be more careful that foreign matter (oil, water, etc.) does not enter the piping when 
installing refrigerant R410A models. Also, when storing the piping, securely seal the 
openings by pinching, taping, etc.

While welding the pipes, be sure to blow dry nitrogen gas through them.

]1

4.1.  Selecting the pipe material

 CAUTION

Do not use existing pipes from another refrigeration system or refrigerant.

Use pipes that have clean external and internal sides without any contamination which 
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.

It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 0.04 oz./100 ft. (40 mg/10 m).

Width across 

fl

 ats

9373370154-01_IM.indb   4

9373370154-01_IM.indb   4

3/14/2012   3:03:51 PM

3/14/2012   3:03:51 PM

Summary of Contents for ASUB18RLAV

Page 1: ...ll Mounted Type APPAREIL INTÉRIEUR Type montage mural UNIDAD INTERIOR Tipo Montado en Pared UNIDADE INTERIOR Tipo montado na parede For authorized personnel only Pour le personnel agréé uniquement Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados TM PART NO 9373370154 ASUB18RLAV ASUB24RLAV ...

Page 2: ...re opening the refrigerant valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain c...

Page 3: ...1 For indoor unit installation Cloth tape 1 For indoor unit installation Name and Shape Q ty Application Tapping screw Big M4 25 mm 8 For wall hook bracket installa tion Air cleaning filter 2 Air cleaning filter frame 2 Drain hose Insulation 1 For installing drain hose Connecting cable 2 For wired remote controller cable connection and simple remote controller cable connection Adapter cable Remote...

Page 4: ...wood screws after confirming using the level indicator that the clamp is horizontal WARNING Install the wall hook bracket level both horizontally and vertically If the wall hook bracket is tilted water will drip to the floor As the weight of the indoor unit is 33 to 40 lbs 15 to 18 kg it should be installed after properly examining the place where it is intended to be installed If the place is not...

Page 5: ...imension B 0 015 0 4 in mm Flare tool for R410A clutch type 1 4 6 35 0 to 0 020 0 to 0 5 11 32 9 1 3 8 9 52 17 32 13 2 1 2 12 70 21 32 16 6 5 8 15 88 25 32 19 7 3 4 19 05 15 16 24 0 When using conventional R22 flare tools to flare R410A pipes the dimension A should be approximately 0 020 in 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring ...

Page 6: ...t remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Instal...

Page 7: ...es with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accide...

Page 8: ... for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Sleeve Screw with special washer Screw with special washer Ring terminal Cable Cable Terminal block Ring terminal Ring terminal Strip 13 32 in 10 mm WARNING Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause hea...

Page 9: ...ith appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input selection Use either one of these types of terminal according to the application Both types of termi nals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the vo...

Page 10: ...p Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 1 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected load Do not impress a voltage exceeding 24 V across pins 1 2 and 1 3 a The allowable current is DC 5 10 mA Recommended DC 5 mA Provide a load resistan...

Page 11: ...ctor to join field cable and wire kit wire Connect the wire with connecting wire with solder Important Be sure to insulate the connection between the wires Option parts External input output wire Insulated connection Field supply Input No Voltage terminal CN17 Controller PCB Input Voltage terminal CN6 Output terminal CN16 CN17 CN16 CN6 Connecting cables Controller PCB Cable tie Field supply 7 FIEL...

Page 12: ...tch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigerant circuit address as the outdoor unit Setting Setting range Type of switch Indoor unit address 0 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 99 Setting example 63 REF AD 10 REF AD 1 Table A Address Rotary Swi...

Page 13: ... 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller Horizontal swing airflow direction 24 00 Default Adjust the horizontal swing airflow direction For horizontal swing equipped mod els 01 Left half 02 Right half Cool air tem perature trigger 30 00 Default Adjust the cool air trigger tempera...

Page 14: ...umber 2 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 11 sec 10 sec 9 sec 1 cycle 12 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF 8 FINISHING Before performing this section perform a sealing test Refer to the installation Manual for the outdoor unit 1 8 1 Connection pipe cable and drain hose Insulate the drain hose if n...

Page 15: ...smission and Re mote controller cable Drain hose Saddle Pipe Outside wall cap Wall Outdoors Sealer putty Field supply GOOD Drain hose Saddle Lifted up Wave End in water PROHIBITED 1 8 2 Installing front cover Fix the indoor unit 1 Please remove the spacer Indoor Unit Remove Spacer 2 Hook the fittings of the indoor unit to the 2 bottom hooks while lowering the unit and pushing it against the wall B...

Page 16: ... burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No cooling No heating Does start and stop air con ditioner operation by remote controller or external device No operation After installation is completed has the proper operation and handling been explained ...

Page 17: ......

Reviews: