En-12
]1
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Fig. B
Code change
Indoor unit
Remote
controller
Confusion
A B C D
A B C D
• Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, 2, referring to the Table B.
Dip switch
“SET 3”
ON
OFF
SW SW SW SW
1 2 3 4
Table B
Custom code
A (Factory setting)
B
C
D
DIP SW
SET 3 SW1
OFF
ON
OFF
ON
DIP SW
SET 3 SW2
OFF
OFF
ON
ON
]1
7.3. Function setting
WARNING
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting
number
Default
Details
Filter
indicator
interval
11
00
Default
○
Adjust the
fi
lter cleaning interval noti
fi
-
cation. If the noti
fi
cation is too early,
change to setting 01. If the noti
fi
cation
is too late, change to setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
○
Enable or disable the
fi
lter indicator.
Setting 02 is for use with a central
remote controller.
01
Disable
02
Display
only on
central
remote
controller
Horizontal
swing
air
fl
ow
direction
24
00
Default
○
Adjust the horizontal swing air
fl
ow
direction.
(For horizontal swing equipped mod-
els)
01
Left half
02 Right half
Cool air
tem-
perature
trigger
30
00
Default
○
Adjust the cool air trigger tempera-
ture. To lower the trigger temperature,
use setting 01. To raise the trigger
temperature, use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
tem-
perature
trigger
31
00
Default
○
Adjust the heat air trigger temperature.
To lower the trigger temperature by
11 degrees F (6 degrees C), use setting
01. To lower the trigger temperature by
7 degrees F (4 degrees C), use setting
02. To raise the trigger temperature,
use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto
restart
40
00
Enable
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency function
such as for power failure etc.
Do not start and stop the indoor unit
by this function in normal operation.
Be sure to operate by the control unit,
converter or external input device.
01
Disable
○
External
control
46
00 Start/Stop
○
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all refrig-
erant systems will be disabled.
* If forced stop is set, indoor unit stops
by the input to the external input
terminals, and Start/Stop by a remote
controller is restricted.
01
Emergen-
cy stop
02
Forced
Stop
Error report
target
47
00
All
○
Change the target for reporting er-
rors. Errors can either be reported in
all locations, or only on the central
remote controller.
01
Display
only on
central
remote
controller
9373370154-01_IM.indb 12
9373370154-01_IM.indb 12
3/14/2012 3:03:56 PM
3/14/2012 3:03:56 PM