En-9

Operation behavior

• Input signal type
The input signal type can be selected. 

Pulse

Edge

The width of pulse 
must be longer than 
200 msec.

It is switched by Dip-sw on the indoor 
unit PCB.

Dip-sw [Set 2-2]

Input signal type

OFF

Edge

ON

Pulse

• When function setting is “Start/Stop” mode
In the case of “Edge” input

Connector

Input signal

Command

Ch1 of CN6 or CN17

OFF 

 ON

Operation

ON 

 OFF

Stop

In the case of “Pulse” input

Connector

Input signal

Command

CN6 or CN17

Ch1

OFF 

 ON

Operation

Ch2

OFF 

 ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

• When function setting is “Emergency stop” mode
In the case of “Edge” input

Connector

Input signal

Command

Ch1 of CN6 or CN17

OFF 

 ON

Emergency stop

ON 

 OFF

Normal

In the case of “Pulse” input

Connector

Input signal

Command

CN6 or CN17

Ch1

OFF 

 ON

Emergency stop

Ch2

OFF 

 ON

Normal

*   All indoor units of same refrigerant system stops when Emergency stop operates. 

• When function setting is “Forced stop” mode
In the case of “Edge” input

Connector

Input signal

Command

Ch1 of CN6 or CN17

OFF 

 ON

Forced stop

ON 

 OFF

Normal

In the case of “Pulse” input

Connector

Input signal

Command

CN6 or CN17

Ch1

OFF 

 ON

Forced stop

Ch2

OFF 

 ON

Normal

*  When the forced stop is triggered, indoor unit stops and Start/Stop operation by a 

remote controller is restricted.

 CAUTION

When forced stop function is used with forming a remote controller group, connect the 
same equipment to each indoor unit within the group.

•  Selection method of functions
“Start/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected with 
function setting of indoor unit.

*1 Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample 

surplus for the connected load.

Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.
*a  The allowable current is DC 5~10 mA. (Recommended: DC 5 mA) 
 

Provide a load resistance such that the current becomes DC 10 mA or less.

 

Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. 
 Connect 

correctly.

When connected to voltage terminals of multiple indoor units with a connected unit, be 
sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

DC power 

supply 12-24 V

Connected unit

Load 

resistance

P.C.B

P.C.B

CN6

CN6

CN6

P.C.B

In

pu

t d

ev

ic

e 1

In

pu

t d

ev

ic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 

resistance

• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device you want to connect, use the no 
voltage terminal ([CN17]).

1
2
3

P.C.B

GND

Ch 1

*c

*c

*d

Ch 2

CN17

Connected unit

*c  Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d The wiring is different from voltage terminals. Be suf

fi

 ciently careful when wiring.

When connected to no voltage terminals of multiple indoor units with a connected unit, 
insulate each indoor unit with relay, etc. as shown on below example.
When connected to multiple indoor units directly, it will cause breakdown.

Po

w

e

r s

u

p

p

ly

 f

o

r r

e

la

y

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Input device 2

Input device 1

K1~K6: Relay 

(Device for DC Current)

P.C.B

K1

P.C.B

P.C.B

CN17

CN17

CN17

K2

K3

K4

K5

K6

9373370154-01_IM.indb   9

9373370154-01_IM.indb   9

3/14/2012   3:03:53 PM

3/14/2012   3:03:53 PM

Summary of Contents for ASUB18RLAV

Page 1: ...ll Mounted Type APPAREIL INTÉRIEUR Type montage mural UNIDAD INTERIOR Tipo Montado en Pared UNIDADE INTERIOR Tipo montado na parede For authorized personnel only Pour le personnel agréé uniquement Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados TM PART NO 9373370154 ASUB18RLAV ASUB24RLAV ...

Page 2: ...re opening the refrigerant valves When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain c...

Page 3: ...1 For indoor unit installation Cloth tape 1 For indoor unit installation Name and Shape Q ty Application Tapping screw Big M4 25 mm 8 For wall hook bracket installa tion Air cleaning filter 2 Air cleaning filter frame 2 Drain hose Insulation 1 For installing drain hose Connecting cable 2 For wired remote controller cable connection and simple remote controller cable connection Adapter cable Remote...

Page 4: ...wood screws after confirming using the level indicator that the clamp is horizontal WARNING Install the wall hook bracket level both horizontally and vertically If the wall hook bracket is tilted water will drip to the floor As the weight of the indoor unit is 33 to 40 lbs 15 to 18 kg it should be installed after properly examining the place where it is intended to be installed If the place is not...

Page 5: ...imension B 0 015 0 4 in mm Flare tool for R410A clutch type 1 4 6 35 0 to 0 020 0 to 0 5 11 32 9 1 3 8 9 52 17 32 13 2 1 2 12 70 21 32 16 6 5 8 15 88 25 32 19 7 3 4 19 05 15 16 24 0 When using conventional R22 flare tools to flare R410A pipes the dimension A should be approximately 0 020 in 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring ...

Page 6: ...t remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape Instal...

Page 7: ...es with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Securely install the electrical box cover on the unit An improperly installed electrical box cover can cause serious accide...

Page 8: ... for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Sleeve Screw with special washer Screw with special washer Ring terminal Cable Cable Terminal block Ring terminal Ring terminal Strip 13 32 in 10 mm WARNING Use ring terminals and tighten the terminal screws to the specified torques otherwise abnormal overheating may be produced and possibly cause hea...

Page 9: ...ith appropriate external dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input selection Use either one of these types of terminal according to the application Both types of termi nals cannot be used simultaneously Voltage terminal CN6 When a power supply must be provided at the input device you want to connect use the vo...

Page 10: ...p Selection method of functions Start Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit 1 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected load Do not impress a voltage exceeding 24 V across pins 1 2 and 1 3 a The allowable current is DC 5 10 mA Recommended DC 5 mA Provide a load resistan...

Page 11: ...ctor to join field cable and wire kit wire Connect the wire with connecting wire with solder Important Be sure to insulate the connection between the wires Option parts External input output wire Insulated connection Field supply Input No Voltage terminal CN17 Controller PCB Input Voltage terminal CN6 Output terminal CN16 CN17 CN16 CN6 Connecting cables Controller PCB Cable tie Field supply 7 FIEL...

Page 12: ...tch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD SW as shown in the Table A for each refrigerant system Set to the same refrigerant circuit address as the outdoor unit Setting Setting range Type of switch Indoor unit address 0 63 Setting example 2 IU AD 10 IU AD 1 Refrigerant circuit address 0 99 Setting example 63 REF AD 10 REF AD 1 Table A Address Rotary Swi...

Page 13: ... 00 Enable Enable or disable the filter indicator Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller Horizontal swing airflow direction 24 00 Default Adjust the horizontal swing airflow direction For horizontal swing equipped mod els 01 Left half 02 Right half Cool air tem perature trigger 30 00 Default Adjust the cool air trigger tempera...

Page 14: ...umber 2 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 11 sec 10 sec 9 sec 1 cycle 12 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF 8 FINISHING Before performing this section perform a sealing test Refer to the installation Manual for the outdoor unit 1 8 1 Connection pipe cable and drain hose Insulate the drain hose if n...

Page 15: ...smission and Re mote controller cable Drain hose Saddle Pipe Outside wall cap Wall Outdoors Sealer putty Field supply GOOD Drain hose Saddle Lifted up Wave End in water PROHIBITED 1 8 2 Installing front cover Fix the indoor unit 1 Please remove the spacer Indoor Unit Remove Spacer 2 Hook the fittings of the indoor unit to the 2 bottom hooks while lowering the unit and pushing it against the wall B...

Page 16: ... burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat or burn damage Are the inlets and outlets free of any obstacles No cooling No heating Does start and stop air con ditioner operation by remote controller or external device No operation After installation is completed has the proper operation and handling been explained ...

Page 17: ......

Reviews: