AirStage ARXK07GALH Installation Manual Download Page 17

En-16

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.

A            B              C           D

A           B            C             D

Indoor 
unit

Remote 
controller

Confusion

Code change

Custom code setting for indoor unit

Set the DIP switch SET 3 SW1, SW2 referring to the Table B.

Dip switch “SET 3”

ON

OFF

SW

1

SW

2

SW

3

SW

4

Table B

Custom code

A (Factory setting)

B

C

D

DIP switch SET3 SW1

OFF

ON

OFF

ON

DIP switch SET3 SW2

OFF

OFF

ON

ON

7.3. Static pressure mode

 

CAUTION

If the applicable static pressure does not match the static pressure mode, the static 
pressure mode may be changed to another mode manually.

Recommended range of external static pressure

AR07/09/12: 0 Pa to 30 Pa
AR14/18/24: 0 Pa to 50 Pa

It is necessary to set up a static pressure mode for each usage of static pressure.
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
•  FUNCTION SETTING can be performed with the wired or wireless remote controller.
  (The remote controller is optional equipment)
•  Refer to the wired or wireless remote controller manual for detailed setting information.

Function Number

Setting Number

Setting Static Pressure

26

00

0 Pa

01

10 Pa

02

20 Pa

03

30 Pa

04

40 Pa

05

50 Pa

31

AR07/09/12 : 10 Pa
AR14/18/24 : 15 Pa

Setting static pressure becomes “30Pa” if AR07/09/12 is set to “04” through “05”.

7.4. Switching of air

fl

 ow direction louver function

When auto louver grille (Optional parts) is attached, set the air

fl

 ow direction louver func-

tion “Valid”.
The air

fl

 ow direction louver of auto louver grille can be operated by the remote controller 

while the air

fl

 ow direction louver function is valid.

• Installation 

method

Set the DIP switch SET 4 SW2, SW2 referring to the Table D.

ON

OFF

  SW SW SW SW
 1 2 3 4

DIP switch “SET 4”

Table D

DIP switch

SET 4 SW2

OFF

Airflow direction louver function “Invalid”
(Factory setting)

ON

Airflow direction louver function “Valid”

9381858019.indb   Sec1:16

9381858019.indb   Sec1:16

11/25/2015   4:11:58 PM

11/25/2015   4:11:58 PM

Summary of Contents for ARXK07GALH

Page 1: ...L DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTER...

Page 2: ...el for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into...

Page 3: ...cation Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Select installation locations that can properly support the weight of the i...

Page 4: ...the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3 1 Unit installation example Connect the locally purchased duct 1 Inlet side Connect the du...

Page 5: ...Duct Locally purchased Intake grille Locally pur chased Air Air Filter Outlet side A 25 mm 25 mm 19 mm 198 mm Inlet side B 109 mm P200 130 mm 38 mm 15 mm 70 mm 11 mm 11 mm AR07 09 12 14 AR18 AR24 A 65...

Page 6: ...it for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipe...

Page 7: ...break 4 3 3 Pipe connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is fo...

Page 8: ...Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less 5 1B ARXK GALH model When using the drain po...

Page 9: ...Drain hose insulation B 3 3 Drain hose insulation B Accessories Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press...

Page 10: ...e product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or...

Page 11: ...sing solid core cables do not use the ring terminal If you use the solid core cables with the ring terminal the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat...

Page 12: ...A01 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected...

Page 13: ...n setting is Operation Stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Operation ON OFF Stop In the case of Pulse input Connector Input signal Command C...

Page 14: ...on parts External input output wire Solder and insulate the connected parts Locally purchased Connection terminals and wiring arrangement In following figure all the possible connectors are connected...

Page 15: ...ptional parts Connection method Connection terminals Auto louver grille terminal CN12 Controller PCB Wiring arrangement Controller PCB CAUTION To protect the cable insulation after opening a knockout...

Page 16: ...t circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses u...

Page 17: ...tatic pressure are as the following table FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Refer to the wired or wireless remo...

Page 18: ...erform an emergency stop If an emergency stop is performed from an external controller all refrigerant systems will be disabled If forced stop is set indoor unit stops by the input to the external inp...

Page 19: ...r error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous...

Reviews: