AirStage ARXK07GALH Installation Manual Download Page 12

En-11

 CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 

the screw. On the other hand, an undertightened screw can cause faulty contact, which 

will lead to a communication failure.

6.4. Connection of wiring

(1)  Remove the cover.
(2)  Connect the connection cable.

Cover

Screw

 

CAUTION

When switching the DIP switch (SW1), be sure to turn off the power supply to the 
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.

GND

L, N: Power supply cable

DIP switch 

(SW1)

X1, X2: Transmission cable

Y1,Y2,Y3: Remote 
controller cable

Cable clamp

For 2-wire type

For 3-wire type

Connect the remote 

controller cable

Y1:Non-polar
Y2:Non-polar
Y3:Do not connect *1

Y1:Red
Y2:White
Y3:Black

Set the DIP switch 
(SW1)

2WIRE
(Factory setting)

3WIRE

*1: If you connect the remote controller cable to the terminal 

Y3, 2-wire type remote controller does not work.

Cable tie (Medium) 
(Accessories)

Avoid covering the air 
inlet with the wiring.

Avoid touching the ceiling with the wiring

Ceiling

Power supply 
cable

Do not bind the power supply cable and other cables together.

6.5. External input and external output (Optional 

parts)

Controller PCB

OFF    ON

SW1 SW2 SW3 SW4

DIP switch 
(SET 2)

Dry contact terminal

(CNA02)

Output terminal  
(CNB01)

Apply voltage terminal

(CNA04)

(CNA03)

(CNA01)

(1) External input

•  Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit 

PCB CNA01 or CNA02.

•  “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

•  Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
•  A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of 
terminals cannot be used simultaneously.)

 Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

Input

de

vic

e 1

Input

de

vic

e 2

Input

de

vic

e 3

Load 

resistance

Load 

resistance

Load 

resistance

*1

DC power supply
12 to 24V

connected unit

*a

*a

*a

P.C.B

CNA01

CNA03

*b

*1  Make the power supply DC12 to 24V. Select a power supply capacity with an ample 

surplus for the connected load.

Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a  The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
 

Provide a load resistance such that the current becomes DC10mA or less.

 

Select very low current use contacts (usable at DC12V, DC1mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

9381858019.indb   Sec1:11

9381858019.indb   Sec1:11

11/25/2015   4:11:56 PM

11/25/2015   4:11:56 PM

Summary of Contents for ARXK07GALH

Page 1: ...L DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTER...

Page 2: ...el for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into...

Page 3: ...cation Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Select installation locations that can properly support the weight of the i...

Page 4: ...the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3 1 Unit installation example Connect the locally purchased duct 1 Inlet side Connect the du...

Page 5: ...Duct Locally purchased Intake grille Locally pur chased Air Air Filter Outlet side A 25 mm 25 mm 19 mm 198 mm Inlet side B 109 mm P200 130 mm 38 mm 15 mm 70 mm 11 mm 11 mm AR07 09 12 14 AR18 AR24 A 65...

Page 6: ...it for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipe...

Page 7: ...break 4 3 3 Pipe connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is fo...

Page 8: ...Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less 5 1B ARXK GALH model When using the drain po...

Page 9: ...Drain hose insulation B 3 3 Drain hose insulation B Accessories Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press...

Page 10: ...e product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or...

Page 11: ...sing solid core cables do not use the ring terminal If you use the solid core cables with the ring terminal the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat...

Page 12: ...A01 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected...

Page 13: ...n setting is Operation Stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Operation ON OFF Stop In the case of Pulse input Connector Input signal Command C...

Page 14: ...on parts External input output wire Solder and insulate the connected parts Locally purchased Connection terminals and wiring arrangement In following figure all the possible connectors are connected...

Page 15: ...ptional parts Connection method Connection terminals Auto louver grille terminal CN12 Controller PCB Wiring arrangement Controller PCB CAUTION To protect the cable insulation after opening a knockout...

Page 16: ...t circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses u...

Page 17: ...tatic pressure are as the following table FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Refer to the wired or wireless remo...

Page 18: ...erform an emergency stop If an emergency stop is performed from an external controller all refrigerant systems will be disabled If forced stop is set indoor unit stops by the input to the external inp...

Page 19: ...r error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous...