AirStage ARXK07GALH Installation Manual Download Page 16

En-15

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1)  IU AD, REF AD SW settings ...... This section (7.1. Setting the address)
(2)  Remote controller settings .........  Refer to the wired or wireless remote controller 

manual for detailed setting information. (Set IU AD, 
REF AD SW to 0)

(3)  Automatic address settings .......  Refer to the outdoor unit manual for detailed setting 

information. (Set IU AD, REF AD SW to 0)

 

CAUTION

Be sure to turn OFF the power before performing the 

fi

 eld setting.

7.1. Setting the address

Manual address setting method

•  If the receiver unit is attached, the indoor unit address and the refrigerant circuit 

address can also be set up through the wireless remote controller.

 

CAUTION

Use an insulated screwdriver to set the DIP switches.

Rotary switch 
Example: “0”

Rotary switch 
Example: “0”

Setting

Setting 

range

Type of switch

Indoor unit address

0 to 63

Setting 
example 
2

IU AD × 10

IU AD × 1

Refrigerant circuit 
address

0 to 99

Setting 
example 
63

REF AD × 10

REF AD × 1

(1) Indoor unit address

  Rotary switch (IU AD × 1)...Factory setting “0”
  Rotary switch (IU AD × 10)...Factory setting “0”
  When connecting multiple indoor units to 1 refrigerant system, set the address at IU 

AD SW as shown in the Table A.

(2) Refrigerant circuit address

  Rotary switch (REF AD × 1)...Factory setting “0”
  Rotary switch (REF AD × 10)...Factory setting “0”
  In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A 

for each refrigerant system.

  Set to the same refrigerant circuit address as the outdoor unit.

•  If working in an environment where the wireless remote controller can be used, the 

addresses can also be set using the remote controller.

•  If setting the addresses using the wireless remote controller, set the indoor unit 

address and refrigerant circuit address to “00”. 

 

(For information on setting using the wireless remote controller.)

Table A

Address

Rotary switch 

setting

Address

Rotary switch 

setting

Refrigerant circuit

REF AD SW

Indoor unit

IU AD SW

× 10

× 1

× 10

× 1

0

0

0

0

0

0

1

0

1

1

0

1

2

0

2

2

0

2

3

0

3

3

0

3

4

0

4

4

0

4

5

0

5

5

0

5

6

0

6

6

0

6

7

0

7

7

0

7

8

0

8

8

0

8

9

0

9

9

0

9

10

1

0

10

1

0

11

1

1

11

1

1

12

1

2

12

1

2

.
.
.

.
.
.

.
.
.

.
.
.

.
.
.

.
.
.

99

9

9

63

6

3

Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.

(3) Remote controller address

i) 3-wire type

  Rotary switch (RC AD SW)...Factory setting “0”

  When connecting multiple indoor units to 1 standard wired remote controller, set the 

address at RC AD SW in sequence from 0.

Setting

Setting range

Type of switch

Remote controller 

address

0 to 15

Setting 

example 

0

RC AD

 

Example

  If 4 indoor units are connected.

RC AD SW

0

RC AD SW

1

RC AD SW

2

RC AD SW

3

Indoor unit

Remote 
controller

Indoor unit

Indoor unit

Indoor unit

RC AD SW

0

1

2

3

4

5

6

7

Address

0

1

2

3

4

5

6

7

RC AD SW

8

9

A

B

C

D

E

F

Address

8

9

10

11

12

13

14

15

ii) 2-wire type

  Rotary switch (RC AD SW)...Factory setting “0”
  Since the remote controller address settings are automatically con

fi

 gured, you do not 

need to con

fi

 gure them.

 If 

con

fi

 guring manually, it is necessary to con

fi

 gure both the indoor unit and the remote 

controller. 

  For details, please refer to the remote controller manual.

9381858019.indb   Sec1:15

9381858019.indb   Sec1:15

11/25/2015   4:11:58 PM

11/25/2015   4:11:58 PM

Summary of Contents for ARXK07GALH

Page 1: ...L DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTER...

Page 2: ...el for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into...

Page 3: ...cation Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Select installation locations that can properly support the weight of the i...

Page 4: ...the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3 1 Unit installation example Connect the locally purchased duct 1 Inlet side Connect the du...

Page 5: ...Duct Locally purchased Intake grille Locally pur chased Air Air Filter Outlet side A 25 mm 25 mm 19 mm 198 mm Inlet side B 109 mm P200 130 mm 38 mm 15 mm 70 mm 11 mm 11 mm AR07 09 12 14 AR18 AR24 A 65...

Page 6: ...it for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipe...

Page 7: ...break 4 3 3 Pipe connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is fo...

Page 8: ...Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less 5 1B ARXK GALH model When using the drain po...

Page 9: ...Drain hose insulation B 3 3 Drain hose insulation B Accessories Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press...

Page 10: ...e product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or...

Page 11: ...sing solid core cables do not use the ring terminal If you use the solid core cables with the ring terminal the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat...

Page 12: ...A01 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected...

Page 13: ...n setting is Operation Stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Operation ON OFF Stop In the case of Pulse input Connector Input signal Command C...

Page 14: ...on parts External input output wire Solder and insulate the connected parts Locally purchased Connection terminals and wiring arrangement In following figure all the possible connectors are connected...

Page 15: ...ptional parts Connection method Connection terminals Auto louver grille terminal CN12 Controller PCB Wiring arrangement Controller PCB CAUTION To protect the cable insulation after opening a knockout...

Page 16: ...t circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses u...

Page 17: ...tatic pressure are as the following table FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Refer to the wired or wireless remo...

Page 18: ...erform an emergency stop If an emergency stop is performed from an external controller all refrigerant systems will be disabled If forced stop is set indoor unit stops by the input to the external inp...

Page 19: ...r error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous...

Reviews: