En-9

6. ELECTRICAL WIRING

 WARNING

Electrical work must be performed in accordance with this Manual by a person certi

fi

 ed 

under the national or regional regulations. Be sure to use a dedicated circuit for the 
unit. 
An insuf

fi

 cient power supply circuit or improperly performed electrical work can cause 

serious accidents such as electric shock or 

fi

 re.

Before starting work, check that power is not being supplied to the all units.

For wiring, use the prescribed type of cables, connect them securely, making sure that 
there are no external forces of the cables applied to the terminal connections.
Improperly connected or secured cables can cause serious accidents such as 
overheating the terminals, electric shock, or 

fi

 re.

Securely install the electrical box cover on the unit. 
An improperly installed electrical box cover can cause serious accidents such as 
electric shock or 

fi

 re through exposure to dust or water.

Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit 
could result.

Use the included connection cables and power cables or ones specified by the 
manufacturer. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable 

current can cause electric shock or 

fi

 re.

Do not modify the power cables, use extension cables, or use any branches in the 
wiring. Improper connections, insuf

fi

 cient insulation, or exceeding the allowable current 

can cause electric shock or 

fi

 re.

Match the terminal block numbers and connection cable colors with those of the 
outdoor unit . Erroneous wiring may cause burning of the electric parts.

Securely connect the connection cables to the terminal board. In addition, secure the 
cables with wiring holders. Improper connections, either in the wiring or at the ends of 
the wiring, can cause a malfunction, electric shock, or 

fi

 re.

Always fasten the outside covering of the connection cable with the cable clamp. (If the 
insulator is chafed, electric discharge may occur.)

Install an earth leakage breaker. In addition, install the earth leakage breaker so that 
the entire AC main power supply is cut off at the same time. Otherwise, electric shock 
or 

fi

 re could result.

Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.

Install the remote controller cables so as not to be direct touched with your hand.

Perform wiring work in accordance with standards so that the air conditioner can be 
operated safely and positively.

Connect the connection cable 

fi

 rmly to the terminal board. Imperfect installation may 

cause a 

fi

 re.

If the supply cable is damaged, it must be replaced by the manufacturer, its service 
agent or similarly quali

fi

 ed persons in order to avoid a hazard.

 CAUTION

Earth (Ground) the unit. 
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a 
telephone earth (ground) cable. 
Improper earthing (grounding) may cause electric shock.

Do not connect power supply cables to the transmission or remote controller terminals, 
as this will damage the product.

Never bundle the power supply cable and transmission cable, remote controller cable 
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.

When handling PCB, static electricity charged in the body may cause malfunction of 
the PCB. Follow the cautions below:

•  Establish an earth (ground) for the indoor and outdoor units and peripheral devices.

•  Cut power (breaker) off.

• Touch metal part of the indoor unit for more than 10 seconds to discharge static 

electricity charged in the body.

•  Do not touch terminals of parts and patterns implemented on PCB.

6.1. Electrical requirement

Voltage rating

230 V

Operating range

198 to 264 V (50 Hz) 
198 to 253 V (60 Hz) 

•  Select the power cable type and size in accordance with relevant local and national 

regulations.

• Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 

wire diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a different 
refrigerant system.
Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform 

the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MFA

ARXK07GALH

0.33 A

20 A

ARXK09GALH

0.33 A

ARXK12GALH

0.43 A

ARXK14GALH

0.80 A

ARXK18GALH

0.93 A

ARXK24GALH

1.03 A

ARXK07GCLH

0.34 A

ARXK09GCLH

0.34 A

ARXK12GCLH

0.44 A

ARXK14GCLH

0.81 A

ARXK18GCLH

0.94 A

ARXK24GCLH

1.04 A

MCA: Minimum Circuit Ampacity
MFA: Main Fuse Ampacity

When the power crossover wiring is done, make it so that the total of the MCA of the 

connected RB units and indoor units does not exceed the 15 A. For RB unit MCA, refer to 

the RB unit installation manual.

If the capacity of connected RB units and indoor units exceeds the upper limit, either add 

breakers or use a breaker with a greater capacity.

B. Earth leakage breaker requirements

Breaker capacity

* Maximum connectable “indoor units” or 

“indoor units + RB units”

30 mA, 0.1 sec or less

44 or less **

100 mA, 0.1 sec or less

45 to 148

*   Heat pump type: indoor units, Heat recovery type: indoor units and RB units.

**  If the total number of units connected to the breaker exceeds 44, either add a 30mA 

breaker, or use breakers with a greater capacity.

6.1.1. Cable 

speci

fi

 cations

Follow the speci

fi

 cations below for the power supply, transmission and remote controller 

cable.

Recommended 

cable size (mm

2

)

Cable type

Remark

Power supply 
cable

2.5

Type60245 IEC57 
or equivalent

2 Cable + earth (ground)

Transmission 
cable

0.33

LONWORKS 
compatible cable

22 AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted pair 
solid core diameter 0.65 mm

Remote 
controller cable 
(2-wire type)

0.33 to 1.25

Sheathed PVC 
cable*

Non-polar 2 core, twisted pair

Remote 
controller cable 
(3-wire type)

0.33

Sheathed PVC 
cable*

Polar 3 core

*: Use shielded cable in accordance with local rules for remote controller cable.

9381858019.indb   Sec1:9

9381858019.indb   Sec1:9

11/25/2015   4:11:55 PM

11/25/2015   4:11:55 PM

Summary of Contents for ARXK07GALH

Page 1: ...L DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTER...

Page 2: ...el for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into...

Page 3: ...cation Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Select installation locations that can properly support the weight of the i...

Page 4: ...the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3 1 Unit installation example Connect the locally purchased duct 1 Inlet side Connect the du...

Page 5: ...Duct Locally purchased Intake grille Locally pur chased Air Air Filter Outlet side A 25 mm 25 mm 19 mm 198 mm Inlet side B 109 mm P200 130 mm 38 mm 15 mm 70 mm 11 mm 11 mm AR07 09 12 14 AR18 AR24 A 65...

Page 6: ...it for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipe...

Page 7: ...break 4 3 3 Pipe connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is fo...

Page 8: ...Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less 5 1B ARXK GALH model When using the drain po...

Page 9: ...Drain hose insulation B 3 3 Drain hose insulation B Accessories Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press...

Page 10: ...e product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or...

Page 11: ...sing solid core cables do not use the ring terminal If you use the solid core cables with the ring terminal the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat...

Page 12: ...A01 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected...

Page 13: ...n setting is Operation Stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Operation ON OFF Stop In the case of Pulse input Connector Input signal Command C...

Page 14: ...on parts External input output wire Solder and insulate the connected parts Locally purchased Connection terminals and wiring arrangement In following figure all the possible connectors are connected...

Page 15: ...ptional parts Connection method Connection terminals Auto louver grille terminal CN12 Controller PCB Wiring arrangement Controller PCB CAUTION To protect the cable insulation after opening a knockout...

Page 16: ...t circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses u...

Page 17: ...tatic pressure are as the following table FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Refer to the wired or wireless remo...

Page 18: ...erform an emergency stop If an emergency stop is performed from an external controller all refrigerant systems will be disabled If forced stop is set indoor unit stops by the input to the external inp...

Page 19: ...r error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous...

Reviews: