AirStage ARXK07GALH Installation Manual Download Page 13

En-12

When connected to Apply voltage terminals of multiple indoor units with a connected unit, 
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below 
example.

DC power supply 
12 to 24V

connected unit

Load 

resistance

P.C.B

P.C.B

CNA01

P.C.B

Input

de

vic

e 1

Input

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 

resistance

CNA01

CNA01

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

P.C.B

GND

Ch 1

Ch 3

*c

*c

*c

*d

Ch 2

CNA02

CNA04

connected unit

*c  Select very low current use contacts (usable at DC12V, DC1mA or less).
*d  The wiring is different from Apply voltage terminals. Be suf

fi

 ciently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 
insulate each indoor unit with relay, etc. as shown on below example.

P

o

w

e

r s

u

p

p

ly

 f

o

r r

e

la

y

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

K1

P.C.B

P.C.B

CNA02

K2

K3

K4

K5

K6

CNA02

CNA02

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

 Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB. 

Pulse

The width of pulse 
must be longer than  
200msec.

Edge

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

 When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

 Operation

ON 

 OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Operation

Ch2

OFF 

 ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

 When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Emergency stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Emergency stop

Ch2

OFF 

 ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates. 

 When function setting is “Forced stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Forced stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Forced stop

Ch2

OFF 

 ON

Normal

*  When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a 

remote controller is restricted.

*  When forced stop function is used with forming a remote controller group, connect the 

same equipment to each indoor unit within the group.

• Selection method of functions

“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected 
with function setting of indoor unit.

 Forced thermostat off function

[“Edge” input only]

Connector

Input signal

Command

Ch3 of CNA03 or CNA04

OFF 

 ON

Thermostat off

ON 

 OFF

Normal

9381858019.indb   Sec1:12

9381858019.indb   Sec1:12

11/25/2015   4:11:57 PM

11/25/2015   4:11:57 PM

Summary of Contents for ARXK07GALH

Page 1: ...L DE INSTALACI N UNIT INT RIEURE type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTER...

Page 2: ...el for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into...

Page 3: ...cation Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Select installation locations that can properly support the weight of the i...

Page 4: ...the job is done with the panel frame only there is a risk that the unit will come loose Please take care 3 3 1 Unit installation example Connect the locally purchased duct 1 Inlet side Connect the du...

Page 5: ...Duct Locally purchased Intake grille Locally pur chased Air Air Filter Outlet side A 25 mm 25 mm 19 mm 198 mm Inlet side B 109 mm P200 130 mm 38 mm 15 mm 70 mm 11 mm 11 mm AR07 09 12 14 AR18 AR24 A 65...

Page 6: ...it for description of the length of connecting pipe or for difference of its elevation Use pipe with water resistant heat insulation CAUTION Install heat insulation around both the gas and liquid pipe...

Page 7: ...break 4 3 3 Pipe connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the centering is improper the flare nut cannot tighten smoothly If the flare nut is fo...

Page 8: ...Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less 5 1B ARXK GALH model When using the drain po...

Page 9: ...Drain hose insulation B 3 3 Drain hose insulation B Accessories Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press...

Page 10: ...e product Never bundle the power supply cable and transmission cable remote controller cable together Separate these cable by 50 mm or more Bundling these cables together will cause miss operation or...

Page 11: ...sing solid core cables do not use the ring terminal If you use the solid core cables with the ring terminal the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat...

Page 12: ...A01 1 External input Indoor unit can be Operation Stop Emergency stop or Forced stop by using indoor unit PCB CNA01 or CNA02 Operation Stop mode Emergency stop mode or Forced stop mode can be selected...

Page 13: ...n setting is Operation Stop mode In the case of Edge input Connector Input signal Command Ch1 of CNA01 or CNA02 OFF ON Operation ON OFF Stop In the case of Pulse input Connector Input signal Command C...

Page 14: ...on parts External input output wire Solder and insulate the connected parts Locally purchased Connection terminals and wiring arrangement In following figure all the possible connectors are connected...

Page 15: ...ptional parts Connection method Connection terminals Auto louver grille terminal CN12 Controller PCB Wiring arrangement Controller PCB CAUTION To protect the cable insulation after opening a knockout...

Page 16: ...t circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses u...

Page 17: ...tatic pressure are as the following table FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optional equipment Refer to the wired or wireless remo...

Page 18: ...erform an emergency stop If an emergency stop is performed from an external controller all refrigerant systems will be disabled If forced stop is set indoor unit stops by the input to the external inp...

Page 19: ...r error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous...

Reviews: