En-8

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

4.4.  Installing heat insulation

Install the heat insulation material after performing a refrigerant leak check (see the In-
stallation Manual for the outdoor unit for details).

4.4.1. Coupler heat insulation

•  Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid 

pipe of indoor side.

•  After installing the coupler heat insulation, wrap both end with vinyl tape so that there 

is no gap.

•  After affi  xing the coupler heat insulation, secure it with 2 cable ties (large), one on 

each end of the insulation.

•  Make sure that the cable ties overlap the heat insulation pipe.

Coupler heat 
insulation 
(Accessories)

Cover this portion with 
heat insulation.

cable tie (Large) 
(Accessories)

Heat insulation

 

CAUTION

After  checking  for  gas  leaks  (refer  to  the  Installation  Manual  of  the  outdoor  unit), 
perform this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

5.  INSTALLING DRAIN PIPES

 

WARNING

Do  not  insert  the  drain  piping  into  the  sewer  where  sulfurous  gas  occurs.  (Heat 
exchange erosion may occur.)

Insulate the parts properly so that water will not drip from the connection parts.

Check  for  proper  drainage  after  the  construction  by  using  the  visible  portion  of 
transparent drain port and the drain piping fi nal outlet on the body.

 

CAUTION

Do not apply adhesive agent on the drain port of the body.
(Use the attached drain hose and connect the drain piping.)

5.1.  When drain pump is used

•  Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
•  Do not perform a rise, trap and air bleeding.
•  Provide a downward gradient (1/100 or more).
•  Provide supporters when long pipes are installed.
•  Use an insulation material as needed, to prevent the pipes from freezing.
•  Install the pipes in a way that allows for the removal of the control box.

Gap of 1.5 to 2 m

700 mm or less

Horizontal or 

upward gradient

Supporter

Max. 300 mm

Locally arranged pipe

GOOD

VP25 [O.D 
32 mm or more]

Rise

Air bleeding

PROHIBITED

Trap

Observe the following procedures to construct centralized drain pipe fi ttings.

VP30 or more [O.D 38 mm or more]

Downward gradient 1/100 or more

700 mm or less

5.2.  When drain pump is not used (Natural drainage)

 

CAUTION

Set “7.4. Switching of drainage function”
Drain  pump  cannot  be  used  if  it  is  installed  in  wall  mounted  type/floor  standing 
concealed type.

If the drain pump is not used, please replace with the drain cap.

Wall mounted type / 

Floor standing concealed type

Ceiling concealed type

•  Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
•  Do not perform a rise, trap and air bleeding.
•  Provide a downward gradient (1/100 or more).
•  Provide supporters when long pipes are installed.
•  Use an insulation material as needed, to prevent the pipes from freezing.
•  Install the pipes in a way that allows for the removal of the control box.

9374342549_IM.indb   8

9374342549_IM.indb   8

2/15/2019   5:46:02 PM

2/15/2019   5:46:02 PM

Summary of Contents for ARXD007GLEH

Page 1: ...ipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a condotto A uso esclusivo del personale tecnico autori...

Page 2: ...als that have been manufactured speci cally for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or impro...

Page 3: ...Application Operating manual 1 Installation manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor s...

Page 4: ...nst the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A p...

Page 5: ...the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR007 009 012 014 018 Model Set the static...

Page 6: ...5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with...

Page 7: ...orts The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installa...

Page 8: ...break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a ame 4 3 1 Flaring Use special are tool exclusive for R410A 1 Cut the...

Page 9: ...he construction by using the visible portion of transparent drain port and the drain piping nal outlet on the body CAUTION Do not apply adhesive agent on the drain port of the body Use the attached dr...

Page 10: ...ess 20 mm Hose band Drain hose Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as in the gure 2 Be sure...

Page 11: ...touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imp...

Page 12: ...otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the termi...

Page 13: ...pply Refer to Power indicator lamp status following CN150 Connect to the Grille 1 CN151 CN152 CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW...

Page 14: ...oltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the...

Page 15: ...setting Connector Input signal Command 60 09 Ch3 of CNA03 or CNA04 OFF ON No command ON OFF Refrigerant leak 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m...

Page 16: ...AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor...

Page 17: ...he input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting errors Error...

Page 18: ...room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor...