background image

En-9

(1) Ceiling concealed type

Gap of 1.5 to 2 m

100 mm or more

Downward gradient  

2.5 to 5.0 mm

Supporter

Locally arranged pipe

GOOD

VP25 [O.D 32 mm 
or more]

Air bleeding

Rise

PROHIBITED

Trap

Observe the following procedures to construct centralized drain pipe fi ttings.

VP30 or more 
[O.D 38 mm or more]

Downward gradient 
1/100 or more

(2) Wall mounted type/Floor standing concealed type

100 mm 

or more

Downward gradient 

2.5 to 5.0 mm

Locally arranged pipe

GOOD

VP25 [O.D 32 mm 

or more]

Air bleeding

Rise

PROHIBITED

Trap

Observe the following procedures to construct centralized drain pipe fi ttings.

VP30 or more 
[O.D 38 mm or more]

Downward gradient 1/100 
or more

5.3.  Install the drain pipe

(1)  Be sure to use supplied Drain hose 

 and Hose band 

.

 Hose band (Accessories)

Drain 
hole

 Drain hose (Accessories)

Hard PVC side 

Hose band

4 mm or less

20 mm

 Hose band

 Drain hose

Fasten the Hose band 

 at the position where 

horizontal against earth (ground).
The Hose band 

 must be positioned at the right 

side of the Drain hose 

 as in the fi gure.

(2)  Be sure to connect Drain pipe with adhesive (polyvinyl chloride) so that there is no 

leakage.

Applying 
area of 
adhesive

Joint pipe 
(Locally purchased)

Drain pipe (VP25) 

(Locally purchased)

4 mm or less

 

CAUTION

Do not connect to the Drain hole with adhesive. Using adhesive may cause damage 
and water leaks.

(3)  After installing the Drain hose 

, check if the drainage is smooth.

 

CAUTION

To prevent excessive force on Drain hose 1, avoid bends or twists. (To bend or twist 
may cause water leaks.)

(4)  After checking for drainage, attach the Drain hose insulation B 

 to insulate, following 

the instructions as in the fi gures.
To avoid space with Drain hose 

 and Hose band 

, press fi rmly the Drain hose 

insulation B 

.

 Drain hose insulation B 

(Accessories)

Ensure there is 
no space.

9374342549_IM.indb   9

9374342549_IM.indb   9

2/15/2019   5:46:03 PM

2/15/2019   5:46:03 PM

Summary of Contents for ARXD007GLEH

Page 1: ...ipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTERNA tipo a condotto A uso esclusivo del personale tecnico autori...

Page 2: ...als that have been manufactured speci cally for R410A use Because the pressure of the R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated piping material or impro...

Page 3: ...Application Operating manual 1 Installation manual 1 This book Installation template 1 For positioning the indoor unit Washer 8 For installing indoor unit Coupler heat insulation Large 1 For indoor s...

Page 4: ...nst the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space required to service the air conditioner 4 A p...

Page 5: ...the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to prevent water from leaking around the port AR007 009 012 014 018 Model Set the static...

Page 6: ...5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the job is done with...

Page 7: ...orts The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installa...

Page 8: ...break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a ame 4 3 1 Flaring Use special are tool exclusive for R410A 1 Cut the...

Page 9: ...he construction by using the visible portion of transparent drain port and the drain piping nal outlet on the body CAUTION Do not apply adhesive agent on the drain port of the body Use the attached dr...

Page 10: ...ess 20 mm Hose band Drain hose Fasten the Hose band at the position where horizontal against earth ground The Hose band must be positioned at the right side of the Drain hose as in the gure 2 Be sure...

Page 11: ...touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board Imp...

Page 12: ...otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the termi...

Page 13: ...pply Refer to Power indicator lamp status following CN150 Connect to the Grille 1 CN151 CN152 CNA01 Apply voltage terminal For external input CNA03 CNA02 Dry contact terminal CNA04 DIP switch SET 2 SW...

Page 14: ...oltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 to 24V connected unit a a a P C B CNA01 CNA03 b 1 Make the...

Page 15: ...setting Connector Input signal Command 60 09 Ch3 of CNA03 or CNA04 OFF ON No command ON OFF Refrigerant leak 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m...

Page 16: ...AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor...

Page 17: ...he input to the external input terminals and Start Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting errors Error...

Page 18: ...room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor...

Reviews: