background image

©

 AirSense Technology. 2008

Page 7

Stratos-Nano

 

• INSTALLER’S HANDBOOK • Iss. 1

no excessive amounts of cable overflowing from the cable area. All cables should be 
kept within this area, and no cables should be routed to run over the top of any of the 
circuit boards.

It may be desirable for one of the cables to enter the bottom of the detector. This can 
be useful if the PSU is positioned below the detector. If this is to be done, the cable 
entry should be carefully drilled out prior to fitting the detector to the wall, and a gland 
should  be  fitted.  When  the  detector  is  installed,  the  wiring  should  be  run  along  the 
cable duct provided at the left-hand side of the detector and into the cable area before 
being terminated at the screw terminals. Care should be taken to ensure that access to 
the front cover screw is not impeded by the PSU.

The Stratos-Nano is designed to be easy to install and commission. A single switch 

bank is all that needs to be set up to configure the detector.

The switch functions are as follows:

1-2. Alarm factor

   Off, Off = 3, On, OFF = 4, Off, On = 5, On, On = 6 (see note 1)

The lower the Alarm Factor the higher the sensitivity of the detector. In applications 

with a large amount of background dust and smoke, it is often better to reduce the 

sensitivity to reduce the chances of nuisance alarms.

3. Fix alarms

   Off = set by ClassiFire, On = fixed (adds 8 to alarm factor) 

Setting this switch stops the ClassiFire system from modifying the alarm thresholds 

after an initial 15-minute period. This bye-passes the filter contamination 

compensation and the fine-tuning of the alarm thresholds to the environment.

4-5. Flow limit offset

   Off, off = 3, On, Off = 6, Off, On = 20, On, On = 45) see 

note 2.
These switches set the sensitivity of the Airflow monitoring system. In areas with a 

tightly controlled, stable air pressure then 00 can be used to give high sensitivity to 

flow variation. In less controlled environments a higher flow limit offset should be used 

to avoid nuisance Fault reports.

6. Flow delay (sec)

   Off = 240, On = 30

This sets the time for which a flow fault must be present before it is reported. 0 gives 

better immunity to nuisance fault reports, but 1 gives faster flow fault response.

7. Input select 

 Off = power monitoring, On = ClassiFire override

If this switch is set to 0 then the input terminals are used for power supply monitoring. 

In this configuration, opening a link between the input terminals will cause the 

detector to indicate a Fault. If the switch is set to 1, then linking the input terminals 

will reduce the sensitivity of the detector. This is useful if it is known that certain 

normal event are likely to cause an increase in background smoke or dust. (eg opening 

an oven door). A remote switch can be used to desensitise the detector. 

4. Configuration

Summary of Contents for LM80031 Draft

Page 1: ... Installer s Handbook LM80031 Draft Aspirating Smoke Detector ...

Page 2: ...hout notice AirSense Stratos HSSD Micra ClassiFire and Stratos Quadra are registered trademarks of AirSense Technology Stratos Ex FastLearn PipeCAD LDD and SenseNET are trademarks of AirSense Technology Copyright 2008 AirSense Technology Introduction 3 Indicators 4 Inside the Enclosure 5 Installation 6 Configuration 7 Troubleshooting 9 Installation Tips 10 Servicing and Repair 10 Stratos Nano Tech...

Page 3: ... in EN60950 It is designed to operate from Safety Extra Low Voltages and does not generate any hazardous voltages Indicates that the detector is a Class 1 laser product as defined in IEC 60825 1 The unit incorporates a Class 3B embedded laser that must not be removed from the detector as retinal damage may occur if the beam enters the eye If this detector is to form part of an approved fire detect...

Page 4: ... panel or connected monitoring equipment 4 OK illuminates to show normal operation when there are no faults The OK lamp will flash during the 15 minute FastLearn period when the detector is learning its environment 5 Flow illuminates to show that the fault signal is as a result of a flow fault 6 Filter illuminates to show the filter needs replacing 7 Head illuminates to show that the fault signal ...

Page 5: ...he Enclosure 1 Filter 2 Configuration switches 3 APIC or serial I F connection for card 4 Fire relay terminals 5 Pre alarm relay terminals 6 Fault relay terminals 7 I P terminals for connection to APIC or serial i f card 8 Programming connector for upgrading software 9 1 2 3 5 6 7 8 4 ...

Page 6: ...e pushed firmly into the port so that the taper on the port holds the pipe firmly and seal the joint between the detector and the pipe without the need for additional sealant If pipe of a different outside diameter is to be used then an adaptor needs to be bought or made to ensure a good fit Excessive force should not be used when pushing in the pipes It should not be necessary and risks damaging ...

Page 7: ...he chances of nuisance alarms 3 Fix alarms Off set by ClassiFire On fixed adds 8 to alarm factor Setting this switch stops the ClassiFire system from modifying the alarm thresholds after an initial 15 minute period This bye passes the filter contamination compensation and the fine tuning of the alarm thresholds to the environment 4 5 Flow limit offset Off off 3 On Off 6 Off On 20 On On 45 see note...

Page 8: ...siFire histogram data It is often beneficial to set this switch once the commissioning is complete so that in the event of a power cut the detector does not re calibrate itself If the detector is to be moved to a new location or if its environment has changed for some other reason then it is advisable to cycle the power with this switch off so that the detector does recalibrate itself Notes 1 Chan...

Page 9: ...for service Detector will not pass smoke test Check that the detector is not in Fast Learn shown by flashing OK LED Ensure that the detector completed its fast learn in its normal environment If there was residual smoke from a previous smoke test then the detector will desensitise itself Nuisance Flow faults This indicates that the flow monitoring is set too sensitive for the environment The flow ...

Page 10: ... 6 Installation Tips Follow best wiring practice when routing connection cables Keep wiring neat and as short as possible while providing adequate stress relief Use screened cables Perform smoke tests to ensure the sampling holes are capable of detecting smoke Consult relevant standards and codes of practice to ensure installations meet relevant legislation requirements Use an EN54 4 approved powe...

Page 11: ...sitivity range 0 0003µm to 10µm Current consumption XXXXX Relay contact rating 500mA 30V Maximum sampling pipe length 100 metres total Sampling pipe inlets 1 Alarm relays Relays provided for pre alarm alarm and fault Aux alarm and fire 2 available via APIC or serial comms Chamber service intervals Greater than 8 years depending on environment Programming Via dil switch Serial data bus Available by...

Page 12: ...296 Fax 44 0 1438 729137 e mail sales airsense co uk www airsensetechnology com AirSense Technology A division of Kidde Products Ltd Registered office Mathisen Way Colnbrook Slough Berkshire SL3 0HB UK Registered in England No 4622271 A UTC Fire Security Company TECHNOLOGY ...

Reviews: