Stratos-Nano
• INSTALLER’S HANDBOOK • Iss. 1
©
AirSense Technology. 2008
8. Disable auto calibration
Off = auto calibrate enabled, on = auto calibrate
disabled
If this switch is set, then the normal power-up calibration of the detector is bye-
passed and the last stored values are used. This applies to both the airflow calibration
and the ClassiFire histogram data. It is often beneficial to set this switch once the
commissioning is complete so that in the event of a power cut, the detector does not
re-calibrate itself. If the detector is to be moved to a new location, or if its environment
has changed for some other reason then it is advisable to cycle the power with this
switch off so that the detector does recalibrate itself.
Notes:
1. Changing alarm factor starts a new FastLearn.
2. Changing the flow limit offset starts a new flow calibration followed by a flow limit
setup.
NB
☞