6. Maintenance/Adjustment
6
-
4
Symptom Cause Counter
measures
Circuit breaker
trips.
(1) Overloaded
(2) Short-circuit occurred at the load side.
Reduce the load
Get rid of cause of short-circuiting.
Even when
operated at a rated
speed, no voltage or
too low voltage
generated.
(1) Faulty voltmeter
(2) Poor tightening of terminals
(3) Broken or short-circuited winding of
generator main unit
(4) Faulty AVR
(5) Faulty silicon rectifier
(mounted on generator main unit rotor)
(6) Faulty exciter
(7) Broken or short-circuited circuit to
exciter field winding
(8) AVR frequency selection switch is not
set to meet the frequency to be operated.
(9) CP1 for protection of generator
functions.
Check/change
Check/repair
Check/repair
Check/change
Check/change
Check/repair
Check/repair
Check/select
Reset
Too high voltage
generated when set
at the rated
frequency
(50Hz/60Hz),
Voltage will not
drop even when the
voltage regulator
controlling knob is
turned.
(1) Loosened or disconnected wiring, or
connector to AVR
(2) Faulty AVR
(3) Broken wire or poor contact of AVR
variable resistor
Check/repair
Check/change
Repair or change
Unstable voltage
generation
(1) Poor tightening of each terminal
(2) Faulty AVR
(3) Function circuit protector (CP) for AVR
protection
Check/repair
Check/change
Reset
Please contact your nearest dealer if you find it difficult to repair by yourselves.
Please refer to the engine operation manual for troubles concerning the engine.
Summary of Contents for SG
Page 1: ......
Page 3: ......
Page 11: ......
Page 12: ......
Page 17: ......
Page 21: ......
Page 25: ......
Page 39: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 50: ......
Page 51: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ...10 Piping Diagram 10 1 10 1 Fuel piping A090427E ...
Page 65: ......
Page 66: ......