All of the following information and instructions are only for
authorized electricians.
CHAPTER 6
INSTALLATION
6.0
Scope of delivery / Mechanical Installation
A visual inspection upon delivery should be performed including a check to ensure
all components are present. Take the delivery unit out of the box immediately before
installation in order to avoid possible damage and contamination during the transport
as well as at the construction site.
Scope of delivery:
1.
Facade
2.
Terminal compartment
cover
incl. 4x fastening screws
3.
Control board
4.
Plastic housing
with impeller
5.
Guide vane
,
with limited
mounting depth removable
6.
Backdraft shutter
,
removable
7.
Cable support sleeve
x 2
8.
Mounting kit
2x screws with dowels
for a wall mounting
9.
Foam strips
6.1
Preparation for wall mounting
Safety instructions listed in Chapter 1.2 must be observed
!
The fan is supplied as a standard complete unit, which is delivered ready for
connection. The installation and set-up of the fan should be performed only after final
cleaning to avoid damage and contamination of the ventilation unit.
After unpacking and before installation the following points must be checked:
- if any transport damage is noticed,
- broken or bent parts
- free running of the impeller
6.2
Installation
The QuietAir 150 is designed for direct wall mounting. The housing must not be
deformed or warped during the installation. Ensure to choose a flat location for
mounting. Fans can be heavy and are sometimes unwieldy. Proper precautions must
be taken, to ensure the assembly is well supported and stable before lifting into
position. Fans should be mounted only on sufficiently strong and stable nature using
appropriate fasteners. Ensure a sufficient additional flow! If necessary, read an
instruction from DIN 1946-6.
1. Cable outlet in the wall
- Position of the cable outlet in the dark area is variable (fig 4).
- Clearance to the pipe centre depending on the cable outlet r = 83 mm (at a variable
position from 0 up to 360
).
- For an easy assembly, recommended to place outlet as shown (90
rotatable). The
optimal position is at 45
when the cable outlet placed directly at the position of the
cable support sleeve.
- QuietAir 150 Pipe inner diameter =
ᴓ 150 mm
- Clearance to room corners: at least 130 mm from the pipe centre
- During the wiring the side recess for the cable entry in housing (fig 7, Pos.1) must
be broken out.
DANGER
Fig 3