background image

 

1.8 

Operational area  
- Appropriate use: 

QuietAir  150  fans  are  used  to  convey  normal  or  slightly  dusty  (particles  size  <  10 
µm),  little  aggressive  and  humid  air,  into  moderate  climate  and  suitable  area  of  its 
performance  curve  (see  Airflow  Developments  sales  documents  /  Internet). 
Operation  permitted  only  for  fixed  installation  within  buildings.  Maximum  permitted 
medium  and  ambient  temperature  is  40ºC.  QuietAir  150  fans  conform  to  enclosure 
protection  IP45,  protection  class  II  and  according  to  VDE0100  part  701  shall  be 
conformed to install in area 1 of humid areas.     

 

 
 
 
 
 

 
 
 
 
 
 

 

- Rationally foreseeable misuse 

The  fans  are  not  suitable  for  use  under  difficult  conditions  such  as  high  humidity, 
aggressive  media,  longer  downtimes,  strong  pollution,  and  excessive  workload  due 
to climatic, technical or electronic influences. The same applies for the mobile use of 
the  fans  (cars,  aircrafts,  ships,  etc.).  To  perform  under  these  conditions  is  only 
possible with release approval by Airflow Developments, in case of standard version 
it is not applicable. 

 

 

- Prohibited use

  

Misuse of the device is not allowed! Solids or solid impurities > 10 µm in transporting 
medium  as  well  as  liquids  are  not  allowed.  Transporting  medium  which  are 
aggressive against the fan material as well as abrasive media is not allowed. Usage 
of the fan in the explosive environment is prohibited.    
 

 

1.9 

Performance data 

The device type plate is binding for the electrical data; this must be conformed to the 
local supply network.  On the test stand fan performance was complied with DIN EN 
ISO 5801. 
         

 

1.10 
 

Noise data  

The noise data which relate to distances is valid under free field conditions.  
After  installation  the  sound  pressure  level  can  vary  significantly  from  the  catalog 
values  since  it  strongly  depends  on  the  installation  conditions,  for  instance  the 
absorption capacity of the room, the room size etc. 
 

CHAPTER 2 
 

GENERAL NOTES

 

2.0 

Qualification of staff 

 Maintenance and installation work must be carried out only by an approved 

electrician. 

QuietAir  150  fans  should  not  to  be  used  by  children  and  persons  with  reduced 
physical,  mental  or  sensory  capacities,  without  proper  practical  experience  or 
expertise,  unless  they  are  controlled  or  instructed  on  the  product  operation  by  the 
person(s)  responsible  for  their  safety.  Children  are  not  allowed  to  play  with  the 
device.  Cleaning  and  maintenance  must  not  be  carried  out  by  children  without 
supervision.  

 

 

 
 
 

2.1 

 
 
 
 
 
 

Touch protection 

-  QuietAir  150  fans  are  supplied  with  a  standard  suction  side  protective  grid. 
Depending on the installation conditions protection against accidental contact on the 
discharge side may also be required. Appropriate protective grids are available as an 
accessory.   
- According to the installation method (for instance installation in ventilation canals or 
covered aggregates) fans are already protected and in such cases they do not need 
a  protective  grid.  It  should  be  noted  that  the  operator  is  responsible  for  compliance 
with the current requirements and is liable for accidents. 
 

 DANGER

 

Summary of Contents for QT 150VS

Page 1: ...nd Operating Instructions QuietAir 150mm Axial Fan MODEL QT 150VS Variable Speed Fan 50 260m3 hr With Adjustable Timer control Variable Speed with timer Low Energy Quiet Long Life Extra Safe 80000309...

Page 2: ...ance Chapter 3 SPECIFICATIONS DIMENSIONS M1 150 0 10V 3 0 Specifications 3 1 Product lifetime 3 2 Accessories 3 3 Dimensions Chapter 4 FUNCTION 4 0 Function description Chapter 5 CLEANING DEINSTALLATI...

Page 3: ...and accident prevention regulations must be observed All electrical work and commissioning must be carried out only by authorized and qualified electricians Maintenance and installation work must be c...

Page 4: ...rly installed and used for its intended purpose product complies with the valid regulations and CE guidelines at the time of its production 1 5 Transport The fan is factory packed so that it is protec...

Page 5: ...ectrical data this must be conformed to the local supply network On the test stand fan performance was complied with DIN EN ISO 5801 1 10 Noise data The noise data which relate to distances is valid u...

Page 6: ...on inhibit activates the fan for 15 sec to protect the motor from rapid on off switching CHAPTER 3 SPECIFICATIONS DIMENSIONS M1 150 0 10 V 3 0 Specifications Impeller 137 Electrical supply NYM 0 2 x1...

Page 7: ...be limited internally via internal potentiometer settings In delivery condition the full scope of the control range becomes available 2 Scaling Scaling can be set through the internal potentiometer i...

Page 8: ...sible housing parts the external housing of the fan with a damp cloth Do not use any aggressive paint solvent cleaning agents High pressure cleaner or spray water is not permitted 5 1 Cover Dismantlin...

Page 9: ...ter unpacking and before installation the following points must be checked if any transport damage is noticed broken or bent parts free running of the impeller 6 2 Installation The QuietAir 150 is des...

Page 10: ...and wall plugs 3 Backdraft shutter and guide vane If required backdraft shutter scope of delivery can be installed behind the guide vane fig 6 During the housing installation the guide vane must be mo...

Page 11: ...must take place in one wire Insertion of 2 wires in the grommet is not allowed In the wiring make sure that wires are placed not on the board but on the edge along the housing fig 9 10 For LiYY contr...

Page 12: ...with supply cable through NYM O 4 1 5mm 2 Relays with low voltage consumers Connection combined with control line through LiYY 5 0 34mm 2 Wire transfer not over the board 1 Insert and tighten the ter...

Page 13: ...an the following need to be checked regularly Appearance of dust or dirt in the housing on the motor and impeller Free running of the impeller Appearance of excessive vibration and noise In case of pr...

Page 14: ...rminal N L Terminal N and L have to be connected to the 230V operating voltage Terminal 5 Terminal 1 activates the low stage Terminal 6 Terminal 2 activates the high stage Terminal 7 10 VDC Terminal 3...

Page 15: ...rocessing work wherein the setpoint of 10 V the controller will reach the maximum value of 100 Thus in the delivery state complete bandwidth set is available for both setpoint input and speed control...

Page 16: ...peed Note Minimum air operation and minimum rate of air can be achieved by electronic temperature sensors such as the ETR Type see accessories 4 Relay output An operating message will be displayed on...

Page 17: ...5 Schematic overview for QuietAir QT150 VS Fig 17...

Page 18: ...failure in Chapter 8 1 Bearing noise Vibrations see Chapter 8 1 Power consumption according to the specifications on the type plate see Chapter 8 1 8 1 Troubleshooting Safety instructions listed in C...

Page 19: ...ion mechanical loading fatigue and or other effects that could not be directly discerned should be disposed in accordance with local and international laws and regulations The same applies to auxiliar...

Page 20: ...le electrical supply 3 Has not been subjected to issue neglect or damage 4 Has not been modified or repaired by any person not authorised by Airflow Developments Ltd 5 Has been installed in accordance...