Ultima Compact™
Chillers
60 Ultima Compact 30-150kW Technical Manual 9690553 V1.2.0_10_2019
Technical Data
Ecodesign
Notes:
Units
UCCL060DX-2AEE
UCCL070SX-2AL0
UCCL070DX-2AFF
SEPR
1,3,5
5.88
5.97
5.65
SEPR Tier
2 (2021)
2 (2021)
2 (2021)
Annual Electricity Consumption
kWh/a
68855.0
75354.0
80717.0
Rated Refrigerant Capacity P
A
1,3,5
kW
54.6
60.7
61.5
Rated Power Input D
A
kW
20.1
23.3
22.9
Rated EER
DC,A
2.71
2.61
2.69
Declared Refrigerant Capacity P
B
1,3,5
kW
60.6 / 29.0
67.5 / 35.6
68.3 / 32.8
Declared Power Input D
B
kW
15.4 / 8.3
18.2 / 8.6
17.8 / 9.6
Declared EER
DC,B
3.93 / 3.48
3.71 / 4.14
3.83 / 3.41
Declared Refrigerant Capacity P
C
1,3,5
kW
66.2 / 32.0
73.9 / 38.6
74.8 / 36.2
Declared Power Input D
C
kW
11.5 / 6.3
13.9 / 6.9
13.6 / 7.4
Declared EER
DC,C
5.75 / 5.09
5.32 / 5.61
5.51 / 4.88
Declared Refrigerant Capacity P
D
1,3,5
kW
71.5 / 35.1
80.2 / 41.6
81.1 / 39.8
Declared Power Input D
D
kW
8.2 / 4.6
10.1 / 5.2
9.8 / 5.5
Declared EER
DC,D
8.67 / 7.62
7.96 / 7.98
8.31 / 7.28
SSCEE
2,3,5
%
131.4%
153.0%
128.4%
SSCEE Tier
NOT Compliant Tier 1 (2018) NOT Compliant
Rated Cooling Capacity P
rated,c
2,4,5
kW
n/a
60.9
n/a
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
n/a
60.7
n/a
Declared EER
d
35°C
n/a
2.61
n/a
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
n/a
67.5 / 34.9
n/a
Declared EER
d
30°C
n/a
3.25 / 3.67
n/a
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
n/a
38.6 / 0.0
n/a
Declared EER
d
25°C
n/a
4.60 / 0.00
n/a
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
n/a
42.4 / 0.0
n/a
Declared EER
d
20°C
n/a
5.89 / 0.00
n/a
Sound Power Level
dB(A)
n/a
77
n/a
Air Volume
m³/h
n/a
24225
n/a
Off mode P
OFF
kW
n/a
0.035
n/a
Thermostat-off mode P
TO
kW
n/a
0.429
n/a
Standby Mode P
SB
kW
n/a
0.052
n/a
Crankcase heater mode P
CK
kW
n/a
0.064
n/a
Capacity Control
Staged
Staged
Staged
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.
Te
ch
ni
ca
l